1.4 Basic
parameters
1.
MAIN TECHNICAL SPECIFICATIONS & DATA
1.4.1 Provide of rated power under following conditions
table 1
1.4.2 Working reliable under the following conditions
table
2
1.4.3 Working reliable under special conditions
For special conditions appliances the power of the generator must be
correct according the bellow formala and table:
Ph = Pn x K1 x K2
Where:
Ph = Power on the requiered height
Pn = Nominal Power
K1 = 1 for use less than 12hr. Day / 0.9 for use over 12hr. Day
K2 = Coeficient according below table
table
3
Sea level (M
)
Ambient temperature
(
°C
)
Relative humidity
0
20 60%
Sea level (M
)
Ambient temperature
(
°C
)
Relative humidity
<1000 5-40 <90%
0
5
10
15
20
25
30
35
40
45
0
-
-
-
-
1
0.98
0.96
0.94
0.92
0.89
200
-
-
-
0.99
0.97
0.95
0.93
0.92
0.89
0.86
400
-
1
0.98
0.96
0.94
0.92
0.9
0.89
0.87
0.84
600
1
0.87
0.95
0.94
0.92
0.9
0.88
0.86
0.84
0.82
800
0.97
0.94
0.93
0.91
0.89
0.87
0.85
0.84
0.82
0.79
1000
0.94
0.92
0.9
0.89
0.87
0.85
0.83
0.81
0.79
0.77
1500
0.87
0.85
0.83
0.82
0.8
0.79
0.77
0.75
0.73
0.71
2000
0.81
0.79
0.77
0.76
0.74
0.73
0.71
0.7
0.68
0.65
2500
0.75
0.74
0.72
0.71
0.69
0.67
0.65
0.64
0.62
0.6
3000
0.69
0.68
0.66
0.65
0.63
0.62
0.61
0.59
0.57
0.55
3500
0.64
0.63
0.61
0.6
0.58
0.57
0.55
0.54
0.52
0.5
4000
0.59
0.58
0.56
0.55
0.53
0.52
0.5
0.49
0.47
0.46
HE
IG
HT
(
m
.)
TEMPERATURE (Celsius)
HUMIDITY BETWEEN 0-50%
K2
0
5
10
15
20
25
30
35
40
45
0
1
1
1
1
0.99
0.96
0.94
0.91
0.88
0.84
200
1
1
1
0.98
0.96
0.93
0.91
0.88
0.85
0.82
400
1
0.99
0.97
0.95
0.93
0.9
0.88
0.85
0.82
0.79
600
0.99
0.97
0.95
0.93
0.91
0.88
0.86
0.85
0.8
0.77
800
0.96
0.94
0.92
0.9
0.88
0.85
0.83
0.8
0.77
0.74
1000
0.93
0.91
0.89
0.87
0.85
0.83
0.81
0.78
0.75
0.72
1500
0.87
0.85
0.83
0.81
0.79
0.77
0.75
0.72
0.69
0.66
2000
0.8
0.79
0.77
0.75
0.73
0.71
0.69
0.66
0.63
0.6
2500
0.74
0.73
0.71
0.7
0.68
0.65
0.63
0.61
0.58
0.55
3000
0.69
0.67
0.65
0.64
0.62
0.6
0.58
0.56
0.53
0.5
3500
0.63
0.62
0.61
0.59
0.57
0.55
0.53
0.51
0.48
0.45
4000
0.58
0.57
0.56
0.54
0.52
0.5
0.48
0.46
0.44
0.41
TEMPERATURE (Celsius)
HE
IG
HT
(
m
.)
HUMIDITY BETWEEN 50-100%
K2
8
Summary of Contents for DHY2500L/E
Page 31: ......
Page 32: ...MADE UNDER LICENSE OF HYUNDAI CORP SEOUL KOREA by ...