Hyundai Heavy Industries HVF Series Instruction Manual Download Page 16

16

<<  

Vacuum Circuit Breaker Instruction Manual

Hazardous high voltage will cause serious injury,
property damage, or even death.

Before inserting or withdrawing, the breaker should be
open, and also before turning the handle, the manual
locker should be in the unlock position.
If excessive power is applied to the handle when the
breaker is closed, it can cause damage to the product.

고전압은 중상, 재산피해, 혹은 사망을 일으킵니다.

차단기를 인입, 인출시키기 전에 차단기는 반드시 트립(OPEN)
상태이고, manual locker는 반드시 unlock position에
있어야 합니다.
차단기가 투입상태이거나 manual locker가 unlock 상태가
아닌 상황에서 무리한 힘으로 핸들을 돌리면 제품의 파손을
가져올수 있습니다.

Excessive weight can cause serious injury or damage.

To avoid this situation, do not transport the breaker on
a lifting facility in the raised position

과도한 무게가 나가는 제품은 심각한 인명피해, 기타 사고를
일으킬 수 있습니다.

높게 올려진 상태에서 차단기를 이동하지 마시고, 
절대 차단기 밑에 서있거나 지나가는 일이 없어야 합니다.

4) 차단기의 인출

차단기가“Open" 상태인지 확인하십시오.
인출입 핸들을 삽입하고 Interlock lever를
누르십시오. 
그림 4-7과 같이 인출입 핸들을 차단기와
반대 방향으로 누르고, 차단기를 Disconnection
위치로 이동 시킵니다.

4.3.2. SF/GS Type

1) VCB 상태점검

배전반 또는 Cradle에 설치하기 전 VCB가

“Open”되었는지 반드시 확인하십시오.

2) Disconnection(또는 Test) 위치로 장착

차단기를 Cradle의 Disconnection(또는 Test) 
위치에 밀어 넣습니다. 
이때 투입버튼을 눌러 정확한 위치에
삽입되었는지 확인 합니다. 
또한, 그림 4-8과 같이 Truck wheel이
정확히 안착되었는지 확인하여야 합니다.

4) Withdrawing the breaker

After checking that the breaker is
opened, insert the crank handle in the
hole and push the interlock lever down
fully.
Then, push the crank handle down
against the breaker so that the breaker
goes to the disconnection position.

4.3.2. SF/GS Type

1) Check the condition of the breaker

Check the breaker is open before
inserted to the switchgear or cradle.

2) Insertion to the disconnection position

Insert the breaker to the cradle at
disconnection (or test) position. 
At this time, push down the close button
fully for the breaker insertion. 
Check that the wheels of the breaker is
exactly inserted to the cradle as in fig 4-8.

DANGER

위 험

DANGER

위 험

Structure and Operation

구조 및 동작

04

Make sure that the breaker and cradle have the
same rating when inserting and withdrawing the
breaker.

The sticker and name plate with rating are attached to
the product. 

차단기와 크레들의 사양이 일치하는지 반드시 확인하여
주십시오.

크레들과 차단기에 제품 사양이 표시되어 있습니다. 
반드시 확인후 사양이 일치하도록 하십시오.

DANGER

위 험

Fig. 4-7 Withdrawing the ES/FS type /
그림 4-7. ES/FS type VCB 인출방법

Fig. 4-8 Insertion of the SF/GS type(1) /
그림 4-8. SF/GS type VCB 인입방법(1)

Close button

Wheels of the

breaker

Sticker

Summary of Contents for HVF Series

Page 1: ...it breaker This instruction manual should be applied only to HVF Series Vacuum Circuit Breakers This instruction manual does not include all items regarding installation and maintenance procedures For...

Page 2: ...ould be accessible to those persons at all times Signal Words Signal words used in this instruction manual are DANGER WARNING and CAUTION in descending order of urgency Indicates an imminently hazardo...

Page 3: ...touch the main and control circuit while the product is in operation The hazardous voltage can cause electric shocks Do not let the product stay in the DISCONNECTION position with UNLOCK state If the...

Page 4: ...stalling the Breaker 11 3 1 Unloading and Storage 3 2 Unpacking 3 3 Inspection After Unpacking 3 4 Installation 3 5 Inspection Before Operation 3 6 Manual Operation 4 Structure and Operation 13 4 1 Co...

Page 5: ...1141 C HVF1151 D HVF2141 C HVF2151 D HVF3141 C HVF3151 D HVF6111 F HVF6141 F HVF1142 C HVF1152 D HVF1162 D HVF1172 F HVF2142 C HVF2152 D HVF2162 D HVF2172 F HVF3142 C HVF3152 D HVF3162 D F HVF6112 F H...

Page 6: ...xt close open operation without delay Consideration of site altitude If the site altitude is higher than 1000 m dielectric strength of the breaker will be reduced according to the altitude Therefore t...

Page 7: ...B Jack and 3 8 for C D Jack AC Option 1 A B Jack 21 22 C D Jack 3 8 M1 Motor operating mechanism K1 Anti pumping contactor R1 Resistor X0 Plug Connector Y1 Open solenoid Y2 2nd open solenoid Y4 C T op...

Page 8: ...he contact pressure spring is compressed properly to maintain sufficient contact pressure on the moving contact of the vacuum interrupters while the breaker is in the closed position and the tripping...

Page 9: ...e used as AC power supply connecting to the motor or closing circuit 2 8 AC Ry B1 B2 9 VCB HVF Series Fig 2 4 Condenser trip device 2 4 Fig 2 5 Circuit diagram of condenser trip device 2 5 This device...

Page 10: ...g the screw down as shown in Fig 2 7 2 10 2nd Open Solenoid Y2 The 2nd trip solenoid Y2 can be attached to the HYUNDAI HVF circuit breaker putting aside the 1st trip solenoid Y1 so that the circuit br...

Page 11: ...any damage or missing materials 3 Check all accessories and spares supplied Also check to see if these parts are damaged 3 4 Installation Before installing the circuit breaker into the switchgear che...

Page 12: ...ress the OPEN button And be sure to check that the breaker is opened and the CLOSE OPEN indicator displays open 4 Finally check that no tools and materials are left near the breaker Bus bar 3 5 1 2 3...

Page 13: ...Indicator 21 Closing Button 22 Trip Button 23 Name Plate 24 Hole for the charging handle 31 Motor 32 Closing Solenoid 33 Trip Solenoid 34 Limit Switch S3 S21 S22 35 Anti Pumping Contact K1 36 Auxilia...

Page 14: ...essed to insure sufficient contact pressure on the moving contact while the breaker is in the closed position and the tripping spring 13 is compressed for the opening operation 3 Recharging After the...

Page 15: ...disconnection or test position At this time push down the interlock lever fully for easy insertion Check that the wheels of the breaker are inserted into the cradle as fig 4 8 3 Insertion to the conne...

Page 16: ...the breaker is opened insert the crank handle in the hole and push the interlock lever down fully Then push the crank handle down against the breaker so that the breaker goes to the disconnection pos...

Page 17: ...e in the hole to draw in and out Rotate handle about 50 times counterclockwise If operator pulls the center handle out interlock will be released and the breaker will be fully separated from cradle 3...

Page 18: ...ition After lifting the center handle the operator can push the breaker to the cradle until it makes a locked sound 3 Insertion into the connection position Same as the SF GS type method 4 Withdrawing...

Page 19: ...ocker to the unlock state and pull the breaker out slowly The Head of Fixing Screw Improper operation of the breaker can cause product damage The breaker can be withdrawn if the head of the fixing scr...

Page 20: ...year a general visual inspection is to be carried out The outer insulation parts should be wiped with a rag more frequently if the breakers are exposed to dust HVF 5 1 5 1 Failure to maintain the equ...

Page 21: ...re insulation resistance between phases and between pole earth with 1000 V megger if the measured value is less than 500 M check the cause 2 Check insulation resistance between control circuit and ear...

Page 22: ...Motor switch off Motor will not run Spring charged Closing spring not charged Breaker closed Breaker is not in proper position No electrical close signal Breaker open No electrical open signal Check...

Page 23: ...th to prevent any accumulation of dust or dirt Avoid any lubricant on insulation or other electrical parts Moving parts should then be moved slightly to let the grease penetrate and become properly di...

Page 24: ...01746 HVS01746 HVS01747 HVS01753 HVS01753 HVS01753 HVS01753 HVS01726 HVS01745 HVS01745 HVS01745 HVS01746 HVS01746 HVS01747 20 20 20 20 20 20 20 20 20 20 28 28 28 28 28 28 28 28 28 28 38 38 38 38 38 38...

Page 25: ...S02421 HVS02421 HVS02435 HVS03626 HVS03626 HVS03640 HVS03640 HVS03640 HVS01750 HVS01750 HVS01750 HVS01746 HVS03640 HVS03640 HVS03640 HVS03642 HVS03642 HVS03642 38 50 50 50 50 70 70 70 70 70 19 19 36 3...

Page 26: ...26 Vacuum Circuit Breaker Instruction Manual Maintenance Recording Maintenance Recording Sheet Date Signature Remarks Cost Free Engineer Service Agent The Substance of Service...

Page 27: ...27 VCB HVF Series Memo...

Page 28: ...Yurakucho Denki Bldg 1 7 1 Yuraku cho Chiyoda ku Tokyo 100 0006 Japan Tel 81 3 3211 4792 Fax 81 3 3216 0728 Osaka I Room 5th Floor Nagahori Plaza Bldg 2 4 8 Minami Senba Chuo ku Osaka 542 0081 Japan T...

Reviews: