background image

Subject to change without notice.

Edition: 26 Feb. 2020      Ver. A0      Page 5/7

Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.

Note:  To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.
          Disabled for HC034RF.

Press the buttons to select light output at 80% (at initial 10,000 hours) or 100%. 

Note: “Sensor off” and “Twilight” functions are disabled. 

Settings (Remote Control HRC-11)

HRC-11

Press button “RESET”, all settings go back to default settings:
Detection range:100%, hold time:1min, stand-by time:5min,
stand-by dimming level:20%, daylight sensor:lux disable, RX 100%

Reset Settings

Permanent ON/OFF function

Press button “ON/OFF” to select permanent ON or permanent OFF mode.
* Press button “AUTO”, “RESET” to quit this mode.
The mode will change to AUTO Mode after power failure.

AUTO mode

Press button “AUTO” to initiate automatic mode. The sensor starts working and all 
settings remain as before the light is switched ON/OFF.

Note: “Semi-auto” function is disabled. 

ON/

OFF

Power output

Press the buttons to adjust the light brightness during hold-time.

Load Indication:
The light will flash ONCE rapidly after 
receiving the commamd from the 
remote control successfully.

Brig/-

Scene program - 

1-key commissioning

Detection range (for Transceiver only)

Press buttons in zone “Detection range” to set detection range at 100% / 75% / 50% / 10%.

Daylight threshold

1. Press button “Start” to program.
2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, “Stand-by dimming level” to set all 
parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).     
    

For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be:  

    Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all 
    settings are passed on the sensor(s).

& A

4

4h

h

h

Press button “Shift”, the LED on the top left corner is on to indicate mode selection. 
All values / settings in RED are valid for 20 seconds. 

Shift Button

Summary of Contents for HMW38/RF

Page 1: ...A capacitive 1200W resistive Capacitive Operation temperature Ta 20 O C 50 O C Environment IP65 IP rating 20s Warming up Technical Data Mechanical Structures and Installations For more details please...

Page 2: ...RF antenna Rotary switch Infrared remote receiver 1 10V 1 10V L N N L Installation hole 71 5 4 2 37 5 38 3 25 11 8 78 2 87 HC034RF 1 10V output RF grouping by rotary switch or remote control C Attach...

Page 3: ...otary Switch Grouping Functions and Features Photocell Advance TM 868 FSK mode Tri level Control Corridor Function 1 Hytronik builds this function inside the motion sensor to achieve tri level control...

Page 4: ...aximum lifetime of the relay 3 RF Grouping by Rotary Switch Maximum 15 channels Noted channel 0 is not for fast grouping and sensors can only be grouped by remote control Transceiver Receiver 15 chann...

Page 5: ...e Semi auto function is disabled ON OFF Power output Press the buttons to adjust the light brightness during hold time Load Indication The light will flash ONCE rapidly after receiving the commamd fro...