Hytronik HMW25 Manual Download Page 2

Subject to change without notice.

Edition: 26 Feb. 2020      Ver. A0      Page 2/5

Functions and Features

Intelligent Photocell (daylight detection prior to motion detection)

2

The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for 
more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is required that the fixture stays at 
dimmed level during absence.

With insufficient natural light, the sensor 
switches on the light automatically when 
presence is detected. 

With sufficient natural light, the light 
does not switch on when presence is 
detected.

The sensor switches off the light when 
natural light is sufficient, even with 
presence.

Tri-level Control (Corridor Function)

1

Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice 
before switch-off.  The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufficient) -->off; and 2 periods of 
selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.  

Note: if the stand-by time is preset at "+∞", the fixture never switches off but stays at preset dimming level even when natural light is sufficient.

Manual Override

3

* Short Push (<1s): on/off function;   
   On 

 Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this 

                    period, the sensor goes back to normal sensor mode.
   Off 

 On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.

* Long Push (>1s): adjust the hold-time brightness level between10% and 100%. 

Note: if end-user do not want this manual override function, just leave the “push” terminal unconnected to any wire.

   

With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the 
brightness by push-switch, which makes the product more user-friendly and offers more options to fit some extra-ordinary demands:

Semi-auto Mode (Absence Detection)

4

It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, people do not want to have a 
sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no need to have the light on. The 
solution is to apply this “absence detector”:  motion sensor is employed, but only activated on the manual press of the push-switch, the 
light keeps being ON in the presence, and dims down in the absence, then switches off in the long absence.

Note: end-user can choose either function     or function      for application. Default function is manual override.

3

4

Reviews: