background image

INSTALLATION

• Support Installation

1. Determine primary direction of product flow. Figure 4A 

indicates the preferred flow as related to the drive.

2.  Refer  to  “Match-Mark”  numbers  on  ends  of  conveyor 

sections. (Figure 4A) Position them in this sequence near 

the area of installation.

3. Attach supports to both ends of drive section and to one 

end  of  intermediate  or  tail  sections  (Figure  4A  and  4C). 

Hand tighten bolts only at this time.

4. Adjust elevation to required height.

• Ceiling Hanger Installation

If conveyors are to be used in an overhead application, 

ceiling hangers may have been supplied in place of floor 

supports.

Figure 4B shows how a ceiling hanger mounts to a conveyor section. Ceiling 

hangers should be mounted at section joints. For safety information concerning 

conveyors mounted overhead, refer to “Installation Safety Precautions” on Pg 3.

• Conveyor Set-Up

1. Mark a chalk line on the floor to locate the center of the conveyor.

2. Place the infeed section in position.

3. Place the remaining sections on the extended support of the previous section 

(figure 4A).

4.  Fasten  the  sections  together  with  splice  plates  and  pivot  plates  (figure  4C).  

Hand tighten the bolts only at this time.

5. Insure that all bed sections are square.  Refer to page 5 for instructions on how 

to square the beds.

6. Tighten all splice plate and support mounting bolts and lag the conveyor to the 

floor.

7.  Connect  the  power  wires  and  the  EzLogic®  zone  controller  cordsets  (where 

applicable) at the sections joints.

8.  Mount  the  power  supply  (for  the  motor)  and  IOP  (for  the  EzLogic®  System 

-  where  applicable)  to  the  conveyor,  near  the  center.    Connect  AC  power  to 

both.  Connect E24 wiring harness to the power supply, and from the IOP to the 

EzLogic®  System  (where  applicable).    See  page  6  for  more  information  about 

these connections 

NOTE:    See  the  EzLogic®  GEN3  Component  Manual  for  more  information 

about  the  IOP  power  connections  and  for  more  information  about  EzLogic® 

components.

9. Install and wire any auxiliary cables or I/O modules.  Refer to pages 6 and 7 for 

more information about auxiliary connections.

• Electrical Equipment

CONTROLS

Electrical  Code:  All  motor  controls  and  wiring  shall  conform  to  the  National 

Electrical  Code  (Article  670  or  other  applicable  articles)  as  published  by  the 

National Fire Protection Association and as approved by the American Standards 

Institute, Inc.

CONTROL STATIONS

A)  Control stations should be so arranged and located that the operation of the 

equipment is visible from them, and shall be clearly marked or labeled to indicate 

the function controlled.

B)  A conveyor which would cause injury when started shall not be started until 

employees in the area are alerted by a signal or by a designated person that the 

conveyor is about to start.

 

When  a  conveyor  would  cause  injury  when  started  and  is  automatically 

controlled or must be controlled from a remote location, an audible device shall 

be  provided  which  can  be  clearly  heard  at  all  points  along  the  conveyor  where 

personnel may be present. The warning device shall be actuated by the controller 

device  starting  the  conveyor  and  shall  continue  for  a  required  period  of  time 

before the conveyor starts. A flashing light or similar visual warning may be used 

in conjunction with or in place of the audible device if more effective in particular 

circumstances.

 

Where system function would be seriously hindered or adversely affected by 

the required time delay or where the intent of the warning may be misinterpreted  

(i.e., a work area with many different conveyors and allied devices), clear, concise, 

and legible warning shall be provided.  The warning shall indicate that conveyors 

and  allied  equipment  may  be  started  at  any  time,  that  danger  exists,  and  that 

personnel must keep clear. The warnings shall be provided along the conveyor at 

areas not guarded by position or location.

C)  Remotely  and  automatically  controlled  conveyors,  and  conveyors  where 

operator stations are not manned or are beyond voice and visual contact from drive 

areas, loading areas, transfer points, and other potentially hazardous locations on 

the conveyor path not guarded by location, position, or guards, shall be furnished 

with emergency stop buttons, pull cords, limit switches, or similar emergency stop 

devices.

 

All such emergency stop devices shall be easily identifiable in the immediate 

vicinity of such locations unless guarded by location, position, or guards. Where 

the design, function, and operation of such conveyor clearly is not hazardous to 

personnel, an emergency stop device is not required.

 

The emergency stop device shall act directly on the control of the conveyor 

concerned  and  shall  not  depend  on  the  stopping  of  any  other  equipment.  The 

emergency stop devices shall be installed so that they cannot be overridden from 

other locations.

D)  Inactive and unused actuators, controllers, and wiring should be removed from 

control  stations  and  panel  boards,  together  with  obsolete  diagrams,  indicators, 

control labels, and other material which serve to confuse the operator.

NOTE: When installing ceiling hanger rods in an existing building, all methods 

of attachment must comply with local building codes.

CEILING HANGER ROD

(VARILLA COLGADA 

DEL TECHO)

SPACER

(ESPACIADOR)

JAM NUT

(CONTRA TUERCA)

SUPPORT PIPE

(SOPORTE ESTACIONARIO)

JAM NUT

(CONTRA TUERCA)

MOUNTING BOLTS

(TORNILLOS DE MONTAJE)

SIDE CHANNEL

(CANAL LATERAL)

PIPE RETAINER

(ABRAZADERA)

LOCK BOLT

(TORNILLO CANDADO)

SPLICE PLATE

(SPLICE PLATE)

SIDE CHANNEL

(CANAL LATERAL)

MOUNTING BOLT

(TORNILLO DE MONTAJE)

SIDE CHANNEL

(CANAL LATERAL)

SPLICE PLATE

(PLACA DE EMPALME)

PIVOT PLATE

(PLACA PIVOTE)

STATIONARY SUPPORT

(SOPORTE ESTACIONARIO)

CONVEYOR

ITEM               TO 

HYTROL CONVEYOR CO. INC.

JONESBORO, AR 

A

1

2

CONVEYOR

ITEM               TO 

HYTROL CONVEYOR CO. INC.

JONESBORO, AR

A

2

1

FIGURE 4A

4”

Adjust to Desired

Elevation

(ajuse la elevacion

a la altura requerida)

Match-Mark Numbers

(etiquetas de secuencia la de armado)

FIGURE 4B

FIGURE 4C

4

Summary of Contents for 190-E24

Page 1: ...odel 190 E24 190 E24C Manual de Instalación y Mantenimiento con Información sobre Seguridad y Lista de Refacciones LAS REFACCIONES RECOMENDADAS SE RESALTAN EN GRIS IMPORTANT DO NOT DESTROY COPYRIGHT PENDING HYTROL CONVEYOR CO INC IMPORTANTE NO DESTRUIR Hytrol Conveyor Co Inc Jonesboro Arkansas Press Optimized for the Environment Impresión Optimizada para Proteger el Medio Ambiente E24 E24C E24EZ E...

Page 2: ... Drive 8 Center Drive etc 5 If you are in a breakdown situation tell us HYTROL Serial Number Located near Drive on Powered Models NOTE If damage has occurred or freight is missing Contact your Hytrol Integration Partner JONESBORO ARKANSAS Model XX Hytrol Conveyor Company Inc SERIAL 123456 Model TABLE OF CONTENTS INTRODUCTION Receiving and Uncrating 2 How to Order Replacement Parts 2 SAFETY INFORMA...

Page 3: ...pecifically designed for carrying personnel Under no circumstances shall any person ride on any element of a vertical conveyor E Personnel working on or near a conveyor shall be instructed as to the location and operation of pertinent stopping devices F A conveyor shall be used to transport only material it is capable of handling safely G Under no circumstances shall the safety characteristics of ...

Page 4: ... from a remote location an audible device shall be provided which can be clearly heard at all points along the conveyor where personnel may be present The warning device shall be actuated by the controller device starting the conveyor and shall continue for a required period of time before the conveyor starts A flashing light or similar visual warning may be used in conjunction with or in place of...

Page 5: ...ower to the tread rollers in Zone 1 Carton 1 will then move forward causing a gap between itself and carton 2 Figure 5D 2 When carton 1 clears controller A carton 2 will then move forward creating a gap between itself and carton 3 3 This sequence will continue as long as the preceeding carton continues to move forward LOADING THE CONVEYOR SLUG MODE 1 Beginning with the conveyor empty and the zone ...

Page 6: ...urrent controlled on the board that are not protected from misplaced fingers Note that the cover makes it difficult to touch any power A tool will be required to move the DIP switches a plastic tip screwdriver is recommended User Product shall be located away from the user such that touching of the o control is not possible MAINTENANCE EZLogic System EZLogic Accumulation System Connections The Mod...

Page 7: ... is a male 8mm push type connector that mates with the female connector of the EZLogic zone controller When the control board receives a run signal from the EZLogic zone controller it turns on the E24 motor Motor Run Terminal This terminal is used to provide a run signal to the motor control board when EZLogic is not being used such as on the 190 E24 conveyor The type of signal used PNP type This ...

Page 8: ...OFF 310 154 225 OFF ON OFF OFF 290 144 211 ON ON OFF OFF 270 134 196 OFF OFF ON OFF 250 124 182 ON OFF ON OFF 230 114 167 OFF ON ON OFF 210 104 153 ON ON ON OFF 190 95 138 OFF OFF OFF ON 170 85 123 ON OFF OFF ON 150 75 109 OFF ON OFF ON 130 65 94 ON ON OFF ON 110 55 80 OFF OFF ON ON 90 45 65 ON OFF ON ON 70 32 51 OFF ON ON ON 50 25 36 ON ON ON ON IOPUnit PowerSuppyforGEN3EZLogic The model 190 E24E...

Page 9: ...NG POWER 1PH 100 240V 10 2 6 1 4 AMPS 3 AMPS INRUSH PEAK GND NEU L1 Terminals Seperated to Clarify Wiring Details NOTE SINGLE PHASE FIGURE 10B Terminals Seperated to Clarify Wiring Details NOTE CUSTOMER CONNECTION INCOMING POWER 3PH 380 480V 15 20 0 9 AMPS 4 AMPS INRUSH PEAK GND L1 L3 L2 THREE PHASE FIGURE 10C 9 ...

Page 10: ...AMPS 4 AMPS INRUSH PEAK GND L1 L3 L2 BLK BLK GRN BLK BLK GRN BLU BLU WHT BLU GRN BLU BLU 24VDC FAN BLU WHT BLU ORG YEL BLU WHT BLU ORG YEL BLK COM RED 24 BLU BLU WHT BLU WHT BLU ORG ORG YEL YEL BLU WHT BLU BLK 460VAC 5AMP A run contact must be used to control starting and stopping of an E24 transportation type conveyor Un contacto de marcha debe ser utilizada para controlar el arranque y la parada...

Page 11: ...d to control starting and stopping of an E24 transportation type conveyor NOTA Sólo se apague la alimentación de entrada a la unidad de sumi nistro de energía en condiciones de parada de emergencia o por ra zones de mantenimiento Un contacto de marcha debe ser utilizada para controlar el arranque y la parada de un E24 tipo de transporte del transportador Terminals Seperated to Clarify Wiring Detai...

Page 12: ...5 1 35 AMPS 4 5 AMPS PEAK INRUSH GND L1 L3 L2 BLK COM RED 24 GRN GRN BLK BLK BLK GRN BLU WHT BLU BLU WHT BLU BLU BLU BLU BLU WHT BLU WHT BLU ORG ORG YEL YEL BLU BLU WHT BLU WHT BLU GRN BLU BLU BLU Terminals Seperated to Clarify Wiring Details BLK BLK BLK Parallel Use Single Use Adjust DC ok Overload L1 L2 L3 13 14 15 16 DC ok Shut Down A run contact must be used to control starting and stopping of...

Page 13: ...0mA A 150Ω series resistor helps the PNP output limit current draw for most situations voltage out is thus lower as current draw increases Voltage dependent on input power and current draw One output signal See Page 14 o Motor Running Environmental Requirements Temperature The unit shall operate within specified limits over the range of 20 o to 40 C 4 to 120 F The unit can be stored in the range o...

Page 14: ...roller Connector This connector accepts a drive no drive signal from an EZLogic zone controller when used The connector is a male 8mm push type connector that mates with the female connector of the EZLogic zone controller When the control board receives a run signal from the EZLogic zone controller it turns on the E24 motor Motor Run Terminal This terminal is used to provide a run signal to the mo...

Page 15: ...tes information about various faults either by flashing or by remaining in a steady ON state Flash patterns are repeated at four second intervals The indicated faults are as follows One flash Board hardware problem Two flashes Over Voltage Three flashes Under Voltage Four flashes Internal motor fault Five flashes Control Board over temperature shut down Six flashes Extreme over current shut down O...

Page 16: ...199 Wiring Trough Cover Gray Styrene Smoke End Cap for Wiring Trough Cover Optional Wiring Harness 1 ft Long Gender Changer 13 B 00913 MS Pivot Plate 1 1 2 in Flange 3 11 16 in High REF NO PART NO DESCRIPTION 14 B 02112 B 00914 1 9 16 in High Floor Support Frame 6 in High Specify OAW B 12777 B 12778 B 00915 B 00916 B 00917 7 in High Specify OAW 8 in High Specify OAW 9 in High Specify OAW 11 1 2 in...

Page 17: ...B Hex Locknut Nylon Insert ZP 10 24 x 5 8 in Rd Hd Mach Screw ZP REF NO PART NO DESCRIPTION 1 2 3 4 5 P 01489 B 23689 B 03916 SA 039353 090 2558 Side Channel Specify Length Large splice Plate Straight to Straight Bed Spacer Specify BR 1 9 Dia Double Groove Roller Specify BR O Ring 177 in Thick 6 7 8 9 10 11 033 09022 033 09001 094 41501 B 22629 B 20601 PT 107299 PT 104688 E24i TM Unidrive Motor E2...

Page 18: ... 032 70502 032 71003 Alum Pop Rivet 5 32 in Dia EZ Twist Lock for 13 32 in Dia Hole Wiring Harness 12 in Zones Specify Length 24 in OAL 36 in OAL 032 71004 032 71005 032 70606 032 70808 032 70808 48 in OAL 60 in OAL 72 in OAL 84 in OAL 96 in OAL 032 71010 032 70201 108 in and 120 in OAL Wiring Harness 18 in Zones Specify Length 18 in OAL REF NO PART NO DESCRIPTION 032 70502 032 71003 36 in OAL 54 ...

Page 19: ...acer Specify BR Tapered Roller Double Grooved Specify BR E24i Motor E24 Motor Optional Control Card for E24 Motor for use with 033 09002 only Drive Spool Double Groove 1 9 in Dia O Ring 3 16 in Thick 9 10 11 12 13 090 25582 040 201 PT 097895 049 528 040 302 O Ring 3 3 16 ID x 3 16 Thick Green Trans 5 16 18 x 3 4 LG Hex Hd Cap Screw ZP Spacer Plate 2 1 2 x 6 in 5 16 18 Small Flange Locknut ZP 3 8 1...

Page 20: ... Harness Specify Length 24 in Thru 48 in OAL 54 in Thru 60 in OAL 66 in Thru 120 in OAL 8 32 x 1 2 in Lg Rd Hd Mach Screw ZP 16 17 041 801 EB 000003 EB 000004 EB 000005 EB 000006 EB 000007 EB 000008 8 32 Hex Locknut Nylon Insert ZP Power Supply for E24 Motors Specify Size 20 AMP 120 230 VAC 40 AMP 120 230 VAC 20 AMP 380 460 VAC 40 AMP 380 460 VAC 5 AMP 115 230 VAC 5 AMP 460 VAC REF NO PART NO DESC...

Reviews: