Page 29
Maximum current draw of the StandardLine
standard models and the required fusing
resulting from that can be taken from the
table below.
7.2 Cable connections
The table below shows the number and
dimensioning of the cable connections pro-
vided by the various StandardLine housing
types.
Characteristics of metric cable connec-
tions
*) Multiple seal insert
Model
Current draw [A]
Fusing
[A]
SLH03
9.4 - 10.2
1 x 16
SLH06
10.7 - 11.7
3 x 16
SLH09
16 - 17.5
3 x 20
SLH15
15.7 - 17.1
3 x 20
SLH25
25.9 - 28.3
3 x 32
SLH40
41.6 - 45.4
3 x 50
SLH50
51.9 - 56.7
3 x 63
Housing
type
M25
M25
with
MSI*)
M32
M40
SLH03/06/
SLH09
1x
1x
SLH15/25
1x
1x
SLH40/50
1x
1x
Thread
Wrench
size [mm]
Cable diameter
supported [mm]
M25x1.5
30
9 - 17
M25x1.5
with
MSI*)
30
6 (3x)
M32x1.5
36
13 - 21
M40x1.5
46
16 - 28