Page 26
Make connection as follows:
»
Attach cap nut with inner seal ring to
inlet screw joint on the humidifier
housing and tighten.
Do not overtighten the cap nut!
Excessive tightening will destroy the fitting.
Strainer must be placed inside the solenoid
valve.
»
Screw the other hose end cap nut
with its inner seal on a customer-
provided water tap (cap nut internal
thread is ¾“) .
6.2 Water discharge
Risk of scalding!
During blow down, up to 0.3 l/sec are being
drained with a temperature of about 95 °C.
Ensure that the drain hose is reliably fas-
tened and wastewater can drain freely and
pressureless.
Humidifier installation location and wastewa-
ter discharge must be on the same pressure
level. In case of a drain connection on posi-
tive pressure, pls. consult your expert dealer.
Guidelines for water discharge composi-
tion
•
Use flexible water hose
•
Do not buckle drain hose
•
Discharge line and drain pipe material
must be temperature resistant up to
95°C
How to proceed
»
Run a 1 1/4 " drain hose of 250 to
1000 mm length into a pressure-free
outlet according to DIN EN 1717.
The hose must be guided sideways
of the humidifier to prevent ascen-
ding vapor from condensating on the
humidifier`s housing.
»
Fit drain hose to connection stub on
humidifier housing bottom side.
»
Slide pump drain hose onto one of
the grounding clips (s. fig. below).
»
Slide overflow hose of the HyFlow
system separator (if present) onto
the other grounding clip.