Page 51
»
Attach steam cylinder connector plug.
»
Switch breaker back on.
»
Open water supply.
»
Switch on unit and check for leaks after 15-30 minutes
of operation.
If leakage occurs, switch off power supply and repair the leaks,
following safety instructions for work on live components!
9.5
Cleaning Steam Cylinder
Removal
»
Close off water supply.
»
Drain steam cylinder (9) by setting main switch to Pos
II.
»
Disconnect power supply and secure against restart
(switch off control switch, remove main fuses and con-
trol fuse F1+F2).
»
Verify absence of electric current.
»
Remove steam cylinder as described in section “Clean-
ing Coarse Strainer in Cylinder Base.”
»
Open cylinder clamping ring (7) and lift off cover (5) with
heater elements (8).
Cleaning
When using mineral deposit removers or cleaners to clean the
cylinder and heater elements, make sure you thoroughly rinse
the unit before returning reassembling it. Use mineral deposit
removers
only
for cylinder and heater elements.
Note:
Overly strong mechanical cleaning can damage the cylin-
der / heater elements.
»
Remove all deposits. However, small amounts of scale
deposits on the heater elements (8) are harmless.
Assembly
»
Install cylinder (9) as described above in section
“Cleaning Coarse Strainer in Cylinder Base.”