5.4
Steam Manifold
5.4.1
Notes on Installation
These notes are based on a homogeneous
Standard steam manifold installation:
An even distribution of steam manifolds ensures a uniform steam
distribution.
Please use the total hight of the duct!
Minimum distances in order to avoid condensation:
L
min
= 210mm
: distance
„ steam manifold - next steam mani-
fold“
L4
min
= 120mm:
distance „lowest steam manifold - duct bot-
tom“:
L5
min
= 120mm
: distance
„highest steam manifold - duct
ceiling“Installations depending on special designs of air ducts:
Horizontal installation of
steam manifold
Steam Manifold
L1=L2=L3
Duct
Steam Manifold
Air flow
Air flow
direction