Page 17
5.2
Fan Unit (optional)
Note:
The fan unit should be positioned to avoid drafts. In gen-
eral, a minimum height of 2 m is sufficient.
Install the fan unit directly on a wall.
Warning:
•
During operation and a soon afterwards the steam
nozzle is hot! If touched this can cause burns to the
skin.
•
During operation the cross-flow fan rotates. Do not
touch the fan during operation.
•
During operation hot steam discharges from the nozzle.
In the field of the visible steam cloud contact can cause
burns to the skin.
•
During operation the cross-flow fan rotates. Do not
touch the fan during operation.
5.2.1
Fan Unit Type VG
•
Install the fan unit over the steam humidifier.
•
When employing multiple fan units, do not exceed a
maximum distance of 5 m from the steam humidifier.
•
Observe the clearances specified in the diagram below:
Fan Unit
Type
for wall installation
VG 08, 17, 30
Technical Specifications Fan Unit VG
Fan Unit
VG08
VG17
VG30
Quantity of Steam
[kg/h]
8
17
30
Steam Inlet
[mm
φ
]
25
25
40
Condensate Outlet
[mm
φ
]
12
12
12
Airflow Capacity
[cbm/h]
185
185
350
Nominal Output
[W]
35
35
67
Nominal voltage
[V]
230
230
230
Dimensions
W [mm]
441
507
550
H [mm]
171
171
171
D [mm]
180
237
277
Weight
[kg]
4,5
6
7
Sound Level (1m dis-
tance to the source of
noise)
[dB(A)]
50
57
59
Steam
Front View Wall Installation
Side View Wall Installation