TESTING
1)
Activate an alarm or evacuate condition at the control panel.
2)
Check the audible activation of the sounder.
3)
Press the SILENCE SOUNDERS button (or equivalent) and ensure all Sounder type devices have silenced before continuing.
4)
Reset the system from the control panel.
All devices must be tested after installation and thereafter on a periodic basis as required by local codes.
ACOUSTIC OPERATIONAL PERFORMANCE
Hyfire Wireless Fire Solutions Limited
-
Unit B12a, Holly Farm Business Park, Honiley,
Warwickshire, CV8 1NP
-
United Kingdom
www.hyfirewireless.com
TECHNICAL SPECIFICATIONS *
Power supply voltage range
15
-
40 Vdc (24 Vdc standard value)
Activated current range, volume set to HIGH.
Dependent upon tone selected
5
-
8 mA at 24 Vdc
Audible frequency range.
Dependent upon tone selected
440
-
2900 Hz
Maximum sound output, volume set to HIGH.
Valid for all tones
100 dB(A) ± 3
Maximum temperature range
-
25 °C / +70 °C
Maximum humidity
95% RH (without condensation)
Height (base included)
185 mm
Diameter
130 mm
Weight (base included)
270 g
IP rating (EN 54
-
3 certified)
33
IP rating (not certified) **
65
*
Consult the latest version of the TDS
-
CWSXX document for
further information, obtainable
from your supplier.
**
Independently assessed and certified to IPX5 (not part of the
current EN54
-
3 certification).
Picture 14