HV BOILER
INSTALLATION & OPERATING INSTRUCTIONS
Nominal Iron
Pipe length
Pipe Size
10'
20'
30'
40'
50'
60'
80'
100'
150'
3⁄4"
278
190
152
130
115
105
90
79
64
1"
520
350
285
245
215
195
170
150
120
11⁄4"
1050
730
590
500
440
400
350
305
250
11⁄2"
1600
1100
890
760
670
610
530
460
380
Note:
Maximum pipe capacity in ft
3
/hr based on 0.60 specific gravity
gas at pressures of 0.5 psig or less and a 0.3 " WC pressure drop.
TABLE 3 Maximum Gas Pipe Capacity in ft
3
/hr
TABLE 4 Equivalent Pipe Length Chart
Equivalent length of pipe fittings in feet
Nominal Iron
Type of Pipe Fitting
Pipe Size
90° Elbow
Tee
Gate Valve
Gas Cocks
(branch flow)
(full port)
3⁄4"
2.06
4.12
0.48
1.25
1"
2.62
5.24
0.61
1.60
11⁄4"
3.45
6.90
0.81
2.15
11⁄2"
4.02
8.04
0.94
2.50
ELECTRICAL WIRING
Electrical Power Connections
CAUTION
:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation!
ATTENTION: Au moment de l’entretien des commandes,
étiquetez tous les fils avant de les débrancher. Des erreurs
de câblage peuvent entraîner un fonctionnement in-adéquat
et dangereux. S’assurer que l’appareil fonc-tionne
adéquatement une fois l’entretirn terminé.
The electrical connections to this boiler must be made in
accordance with all applicable local codes and the latest edition
of the National Electrical Code, ANSI/NFPA-70. Installation
should also conform with CSA C22.1 Canadian Electrical
Code Part I if installed in Canada. Install a separate 120 volt 15
amp circuit for the boiler. A shut-off switch should be located at
the boiler. The boilermust be grounded in accordance with the
authority having jurisdiction, or if none, the latest edition of the
National Electrical Code, ANSI/NFPA-70.
Line voltage field wiring of controls and other devices must
conform to the temperature limitation of type T wire at
95°F
,
35°C, above room temperature. Use copper conductors with a
minimum size of #14 awg. Low voltage wiring must not be less
than #18 awg with a neoprene, thermoplastic or other
equivalent insulation having a minimum insulation thickness of
0.012 in
,
0.3 mm.
THERMOSTAT INSTALLATION
Always
follow the instructions included with the thermostat to
be used to control the boiler. Proper location of the thermostat
will ensure efficient trouble-free operation of the boiler. Mount
the thermostat to an inside wall at a height approximately five
feet above the floor. Avoid placing the thermostat in areas that
will not provide an accurate measurement of the room
temperature. Locating the thermostat behind a door, in an alcove,
close to a source of thermal radiation or in a drafty area will
cause poor or sporadic heating.
CO DETECTORS
WARNING
:
Installers must follow local regulations with
respect to the installation of CO detectors and follow
the manufacturer’s stated maintenance schedule for
this boiler!