26
P/N 42-9534 8/08 Copyright 2008 Hydrotherm
KN-SERIES GAS-FIRED DIRECT VENT CAST IRON BOILERS – CONTROL MANUAL
Table 7
SETUP
menus
(continued)
(
see Table 9, page 30 for explanations
)
Level 1
next item
to select
Level 2
next item
to select
back one level
Level 3
next item
to select
back one level
Default {Range}
to change value
to accept value and return to previous menu level
Typical line
(Display shows four lines at a
time; cursor indicates active
line)
PUMP OPTIONS
SYSTEM PUMP
POST PRG TIME
2 minutes {1 to 60 minutes}
POST PRG TIME 2M
ALWAYS ENABLED OFF
SUMMER PUMP JOG:OFF
ALWAYS ENABLED
OFF {ON or OFF}
SUMMER PUMP JOG:
OFF {Day of week, MON , TUE, etc.}
LOCAL PUMP
DELTA TEMP ENAB
OFF {ON or OFF}
DELTA TEMP ENAB OFF
DELTA TEMP 10°
POST PRG TIME 2M
ALWAYS ENABLED OFF
DELTA TEMP
10°F {0 to 50°F}
POST PRGE TIME
2 minutes {1 to 60 minutes}
ALWAYS ENABLED
OFF {ON or OFF}
PUMP/VALVE OPTION
MASTER PUMP/VALVE
REMAINS ON:
OFF {ON or OFF}
MASTER PUMP/VALVE
REMAINS ON: OFF
FLOW PROVE:
10 seconds {10 to 240 seconds)
FLOW PROVE: 10S
NIGHT SETBACK
SETBACK ENTRY
1 {1 through 4}
SETBACK ENTRY 1
ENTRY IS OFF
SETBACK 20°F
SETBACK TIME
ENTRY IS
OFF {ON of OFF}
SETBACK
20 °F {0 to 50°F}
SETBACK TIME
START DAY
MON {SUN, MON, TUE, WED, THU, FRI, SAT}
START DAY MON
TIME 10:00 PM
END DAY FRI
TIME 9:00 PM
TIME
12:00 AM {Time, AM or PM}
END DAY
MON {SUN, MON, TUE, WED, THU, FRI, SAT}
TIME
12:00 AM {Time, AM or PM}
OPTIONS
TEMP SCALE
°F {°F or °C}
TEMP SCALE °F
KEY CLICK ON
SKIP PASSW ON
BRIGHTNESS 50%
KEY CLICK
ON {ON or OFF}
SKIP PASSWORD
ON {ON or OFF}
BRIGHTNESS
50% {12, 25, 37, 50, 62, 75, 87, 100%}
Control menus and adjustments
(continued)
6