25
P/N 42-9534 8/08 Copyright 2008 Hydrotherm
KN-SERIES GAS-FIRED DIRECT VENT CAST IRON BOILERS – CONTROL MANUAL
Level 1
next item
to select
Level 2
next item
to select
back one level
Level 3
next item
to select
back one level
Default {Range}
to change value
to accept value and return to previous menu level
Typical line
(Display shows four lines at a
time; cursor indicates active
line)
KN
V X.X
Shows fi rmware version number
KN
SERIES V 2.45
BOILERS
# OF BOILERS
1 {1 to 16} — display only — gives the number of boilers on a HeatNet network
# OF BOILERS 1
LEAD BOILER # 1
HEAT BAND 30°F
HNT 123456789
¹₀¹₁¹₂¹₃¹₄¹₅¹₆
LEAD BOILER #
Always shows “1” — display only, not adjustable
HEAT BAND
30 °F {10 to 50°F}
HEAT NET BOILERS
123 . . .
Display only, on MASTER boiler only — shows the H-NET ADDRESS of each boiler
detected on the HeatNet network (from 1 to 16)
NOTE that the MASTER address, actually 255, is shown as 1 in this display
SETPOINTS
LOCAL SETPT or
SYSTEM SETPT
180°F {40 to 180°F}
SYSTEM SETPT will appear if a sensor is connected to the SYS/DHW HEADER
terminals. Otherwise, the display will show LOCAL SETPT.
LOCAL SETPT 180°F
OPERATE LIM 10°F
OP LIM BAND 215°F
SETPT SOURCE AUTO
OPERATE LIMIT
205°F {145 to 205°F}
OP LIM BAND
10°F {1 to 50°F}
SETPT SOURCE
AUTO {AUTO, 4-20MA} (NOTE: If 4-20MA is selected, the control setup menu
will automatically open the ADVANCED SETUP | 4-20MA INPUT menu to allow
setting the operating levels to match the 4-20MA remote signal controller
requirements.)
OUTDOOR AIR
OA RESET
OFF {ON or OFF}
OA RESET OFF
WARMWEATHER SD NO
OA SETPOINT 68°F
SET OA SETPOINTS
WARM WEATHER SD
NO {YES or NO}
WWS SETPOINT
68°F {40 to 100°F}
If the OA OVR input is closed, outdoor reset and warm weather shutdown are
overridden. The boiler will run at LOCAL/SYSTEM SETPOINT.
SET OA SETPTOINS
WATER TEMP
AT
HIGH OA TEMP
140°F {60 to 150°F}
70°F {50 to 90°F}
WATER TEMP 40°F
AT
HIGH OA TEMP 70°F
NEXT
WATER TEMP
AT
LOW OA TEMP
180°F {70 to 180°F}
10°F {-35 to +40°F}
WATER TEMP 180°F
AT
LOW OA TEMP 10°F
BACK
Table 7
SETUP
menus (
see Table 9, page 30 for explanations
)
To enter Setup: From STANDBY, hold
for 5 seconds. (If SKIP PASSWORD is set to OFF, you will have to enter the password.)
Then press
with cursor on
SETUP
.
Make sure there is no call for heat at the boiler before attempting to perform setup adjustments.
To return to STANDBY, press/release
until the display returns to standby, or turn boiler ON/OFF switch off , then on.
Control menus and adjustments
(continued)
6