background image

FIGURE 1.16

PROCEDURE A: Select gas pipe size which will result in a pressure drop of less than 0.3" W.C.

for natural gas or 0.5" W.C. for propane, following example below. 

Example: Boiler Model EW-125 is to be installed. Distance from existing gas meter to installation site is 20 ft.
What pipe size must be used? Local utility indicates heating value of natural gas being supplied is 1020 Btu per
cu.ft. Determine cubic feet of gas per hour for above boiler model:

125,000 Btu per hour

= 122.5 cu.ft. per hour

1020 Btu per cu.ft.

1. Find 20 ft. in upper portion of the table for natural gas under “Length of Pipe, Feet” heading.
2. Moving down the column, match required capacity. Higher capacity acceptable. In our case it is 190 cu.ft.
3. Move to left-hand column “Nominal Iron Pipe Size, Inches”;  read required pipe size. In our case it is 3/4
4. Take into account the effects of pipe fittings when determining the correct pipe size.

10

STEP 4: INSTALLING & TESTING GAS PIPING

10

20

30

40

50

60

70

80

90

100

125

150

175

200

10

20

30

40

50

60

70

80

90

100

125

150

Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied

Petroleum gases (at 11 Inches of Water Column Inlet Pressure)

(Based of a Pressure Drop of 0.5 Inch Water Column)

.326

32

22

18

15

14

12

11

11

10

9

8

8

7

6

.493

72

49

40

34

30

27

25

23

22

21

18

17

15

14

.622

132

92

73

63

56

50

46

43

40

38

34

31

28

26

.824

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1.049

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1.380

1,050

730

590

500

440

400

370

350

320

305

275

250

225

210

1.610

1,600 1,100

890

760

670

600

560

530

490

460

410

380

350

320

2.067

3,050 2,100 1,650 1,450 1,270 1,150 1,500

990

930

870

780

710

650

610

2.469

4,800 3,300 2,700 2,300 2,000 1,850 1,700 1,600

1,500 1,400 1,250 1,130 1,050

980

3.026

8,500 5,900 4,700 4,100 3,600 3,250 3,000 2,800

2,600 2,500 2,200 2,000 1,850 1,700

4.026

17,500 12,000 9,700 8,300 7,400 6,800 6,200 5,800

5,400 5,100 4,500 4,100 3,800 3,500

1/4"
3/8"
1/2"
3/4"

1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
4"

Nominal

Iron Pipe

Size,

Inches

Internal

Diameter,

Inches

Length of Pipe, Feet

Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of

0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column

(Based on a 0.60 Specific Gravity Gas)

Nominal

Iron Pipe

Size,

Inches

Length of Pipe, Feet

275

189

152

129

114

103

96

89

83

78

69

63

567

393

315

267

237

217

196

185

173

162

146

132

1071

732

590

504

448

409

378

346

322

307

275

252

2205

1496 1212

1039

937

834

771

724

677

630

567

511

3307

2299 1858

1559

1417

1275

1180 1086

1023

967

866

787

6221

4331 3465

2992

2646

2394

2205 2047

1921 1811

1606

1498

1/2"
3/4"

1"
1-1/4"
1-1/2"
2"

Summary of Contents for EW2-1203

Page 1: ...om a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service...

Page 2: ...ent but not related to personal injury hazards AVERTISSMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d explosion ou pour v...

Page 3: ...1 or 2 Installation Codes for Gas Burning Appliances and Equipment and with Standard C S A C22 1 Canadian Electrical Code Part 1 and Part 2 and or local codes In the Commonwealthof Massachusetts the...

Page 4: ...rdance with Section 5 3 Air for Combustion Ventilation of the latest edi tion of the National Fuel Gas Code ANSI Z223 1 and all applicable local building codes Failure to provide adequate combustion a...

Page 5: ...ay result PROCEDURE A Install vent tapping assembly components and relief valve discharge piping For Models EW 85 100 125 supply outlet is on the top front of the boiler and vent fitting assembly tapp...

Page 6: ...small and setting it by temperature can be accomplished with a contact thermometer PUMPED BLEND An additional circulator can also be used to provide a return water temperature blend This method works...

Page 7: ...ater chiller the chilled water must be piped in paral lel with the boiler using appropriate valves to prevent the chilled medium from entering the boiler Figure 1 9 When boilers are connected to heati...

Page 8: ...additional appliance this will cause fire or carbon monoxide poisoning PROCEDURE A Mount draft hood and spill switch on boiler 1 Install draft hood on boiler If draft hood shroud has a hole near the...

Page 9: ...operate con tinuously 5 Test for spillage at draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from cigarette cigar or pipe 6 After it has...

Page 10: ...olumn 326 32 22 18 15 14 12 11 11 10 9 8 8 7 6 493 72 49 40 34 30 27 25 23 22 21 18 17 15 14 622 132 92 73 63 56 50 46 43 40 38 34 31 28 26 824 278 190 152 130 115 105 96 90 84 79 72 64 59 55 1 049 52...

Page 11: ...P 5 WIRING THE BOILER All electrical wiring must be in accordance with require ments of authority having jurisdiction or in absence of such requirements to National Electric Code NFPA 70 latest editio...

Page 12: ...60HZ OR OPER CONTROL THERMOSTAT 115V 60HZ OR OPER CONTROL THERMOSTAT BLUE FIGURE 1 19 WIRING DIAGRAM OPERATION SEQUENCE FOR BOILERS WITH STANDING PILOT VENT DAMPER L8148E AQUASTAT RELAY STANDING PILO...

Page 13: ...CLOSED DURING STANDBY MOTOR DRIVES VENT DAMPER TO CLOSED POSITION AND TT TT T1 FACTORY WIRED FIELD WIRED CIRC MOTOR CIRCULATOR MV PV PURP ROLLOUT Z W 1K VENT DAMPER 2 3 4 1 T TV IGNITOR SENSOR GAS VAL...

Page 14: ...T1 TO ADDITIONAL ZONES H1 C1 ZONE CIRCULATOR TH1 ZONE T STAT C2 ZONE CIRCULATOR TH2 ZONE T STAT ZR1 ZONE RELAY RA832A OR EQUIVALENT ZR2 ZONE RELAY RA832A OR EQUIVALENT H1 HI LIMIT AQUASTAT GV GAS VAL...

Page 15: ...operating In case of a damper malfunction the damper blade may be manually placed in the full open position to permit burner operation To accomplish this follow the instructions on the damper 5 Allow...

Page 16: ...ckwise to increase gas flow increase input Turn adjusting screw counterclockwise to decrease gas flow decrease input In no case should final manifold pressure setting vary more than 2 from factory set...

Page 17: ...g the top of the burners and enclosing the pilot 7 Find pilot Follow metal tube from gas control The pilot is between the central burner tubes behind the base door 8 Turn knob on gas control countercl...

Page 18: ...ion rust or corrosion Clean and replace as necessary Check tightness of joints seal all joints where necessary 2 Check boiler flue passageways in the boiler sections for any blockage or soot accumulat...

Page 19: ...at ODOR EXCESSIVE MOISTURE IN BUILDING 1 Leak in piping 2 Carbon build up in flueways 3 Blocked chimney 4 Downdrafts incorrect termination YELLOW FLAME CARBON BUILD UP 1 Unit overfired 2 Air shutter m...

Page 20: ...fils SASSURER QUE LE MOTEUR SOIT SITUE A GAUCHE MONTER LE VOLET DE VENTILATION AU DESSUS DU COUPE TIRAGE LA FLECHE DE DIRECTION DE LECOULEMENT POINTE VERS LE HAUT FIGURE 1 12 FIGURE 1 14 FAISCEAU DE...

Page 21: ...21...

Page 22: ...2 2 2 2 11 Dome 5 01 2100 1 1 1 Dome 6 01 2102 1 Dome 7 01 2103 1 1 12 Pressure Relief Valve 22 1203 1 1 1 1 1 1 13 Vent Fitting 56 5430 1 1 1 1 1 1 14 Nipple 3 4 x 9 53 1133 1 1 1 1 1 1 15 T Baffles...

Page 23: ...ed Side Plate BM 3340 1 1 1 1 1 1 42 Drain Valve 51 1201 1 1 1 1 1 1 43 1 1 4 x 3 4 x 1 1 4 Tee 56 1603 1 1 1 1 1 1 44 1 1 4 x 3 Nipple 53 1250 1 1 1 1 1 1 45 Taco Circulator Flange 09 1921 1 1 1 1 1...

Page 24: ...5211 CREEKBANK ROAD MISSISSAUGA ONT CANADA L4W 1R3 905 625 2991 FAX 905 625 6610 260 NORTH ELM STREET WESTFIELD MA 01085 413 564 5515 FAX 413 568 9613...

Reviews: