Troubleshooting

Moby Controller is 

ON but flaps do not 

operate on manual

Moby Controller is 

ON but flaps do not 

operate on manual

Go to System 

Information.               

Do you notice N2K 

error and Temperature 

Offline?

1) Open the air unit.

 

2) When buttons ↑↓←→ 

are pressed, do you 

notice the red lights on 

the PCB on? 

1) Is there power supply 

to the air unit? 

2) Are the fuses ok?

3) Does the PCB has 

power supply?

Use a jumper wire 

between COM and 

LDRU, RDLU,DN,UP.

Do you notice relevant 

red lights on?

1) Reset or replace the fuses.

2) Check the wires which are 

connected to PCB and 

transformer.

3) Replace the transformer.

When the red lights are 

on, does the compressor 

work?

Replace air unit PCB.

When the red lights are 

on, do the relevant 

solenoids operate?

1) Check for replacement the 

compressor relay and 20A 

fuses.

2) The compressor is burned.

Yes 

No

Do you get the 

relevant output?

No

Yes 

Yes 

No

Yes 

No

Yes 

No

Burned solenoid or 

pilot.

Air leakage by faulty 

flap or air unit.

Yes

No

NMEA Network 

communication failure 

due to cabling or PCB 

fault.

Yes

No

Summary of Contents for AIR UNIT MAX

Page 1: ...Hydro Tab Marine Engineering Hydrotab BT Series INSTALLATION MANUAL AIR UNIT MAX NMEA 2000 NMEA 0183 Hydro Tab Marine Engineering...

Page 2: ...n patents pending Declaration of conformity This product conforms to the following Electromagnetic Compatibility EMC regulations and standards for use in marine environments CE EN 60945 Technical info...

Page 3: ...Connection 5 Technical Data Dimensions 5 Air Unit Max Direct Installation Diagram 6 Air Unit Max Installation Diagram on existing NMEA network 6 Air Unit Max Electrical Diagram 7 Air Unit Max Pneumat...

Page 4: ...ING FREE OF EXPLOSIVE OR FLAMMABLE GASES THE AIR UNIT MUST BE INSTALLED IN A COMPARTMENT THE AIR UNIT MUST BE INSTALLED 20cm BELOW ANY SURFACE THAT LOCATES ABOVE IT WARNING 1 2 444mm Drill 3 You will...

Page 5: ...and connect it to the Air Unit Hydro Tab Marine Engineering Technical Data Dimensions A 259 mm B 143 mm C 459 mm Compressor power 380 W Air compressor type Brushless oil free Voltage 24 V Amps 15 A In...

Page 6: ...A 2000 Flybridge OPTIONAL controller CABLE 3m MF Moby Controller Direct Installation Diagram CABLE 10m FF In case a new NMEA 2000 instrument to be added a proper NMEA Network must be built USE INLINE...

Page 7: ...4V 12 24V NMEA 2000 T1 M Compressor 500 AIR N2 V2 1 F1 F1 3A 24V DC 230V DC 24V DC 230V DC 24V DC 230V DC C5 Timer Switch 12V Tr1 1 2 3 4 LEFT RIGHT 1 2 3 4 LEFT RIGHT SYMBOL Part No Description C1 C4...

Page 8: ...1 PNE 01242C FILTER 1 36 RUB 00162 PCB RUBBER BASE 1 37 RUB 00163 VENTOURI RUBBER SUPPORT 1 44 ELE 00057 CABLE GLAND PG13 5 1 Valves Assembly see below Spare Parts Valves Assembly 54 53 55 50 52 56 51...

Page 9: ...mper wire between COM and LDRU RDLU DN UP Do you notice relevant red lights on 1 Reset or replace the fuses 2 Check the wires which are connected to PCB and transformer 3 Replace the transformer When...

Page 10: ...tab gr product registration In case the dealer sells separate units of Interceptors Air Units and Controllers that constitute a full system that is not initially sold as a complete system by Hydrotab...

Page 11: ...Hydro Tab Marine Engineering Notes...

Page 12: ...Hydro Tab Marine Engineering 4 Papazoglou str GR 17778 Athens Greece email info hydrotab gr website www hydrotab gr REV C Hydro Tab Marine Engineering...

Reviews: