Electrical Connections 
 
Important Note: 

In the case of connecting LAN- and M-Bus cables over long distances or 
between buildings we recommend the interconnection of a lightning 
arrester. We qualified the following types: 

-

 

for M-Bus connections: Dehn BD48 

-

 

for LAN connections: Dehn DPA MCA T6RJ45 S48  

When connecting M-Bus devices to the IZAR CENTER, you do not have to 
interrupt power supply  
 

Number Description 

16  110..230 V AC 

5,6 Protective earth

 

29,31,33 M-Bus  
30,32,34 M-Bus output - 

1 M-Bus Repeater input 
2 M-Bus Repeater input 

68  Connector for LAN 
66  Connector for USB 
67  Connector Mini DIN (8 pol.) for connecting PC, Modem (RS232 interface) 
20  Sticker with serial number and MAC Adress

 

65 Black hook 

 

 

Power supply:

  

110 ... 230 V AC (16), Euro-Norm shock-proof plug. 

Protective Earth:

 

Connect clamp 5 or 6 to a protective earth potential.

 

  

 

 

Important Note: 

Protective earth must be connected to IZAR CENTER. 

M-Bus Devices:

 

M-Bus devices are connected to the M-Bus clamps (see table). The M-Bus is 
polarity independent, but you have to use one + and one - output for each 
branch of the M-Bus network. All M-Bus outputs are parallel.

 

Repeater:

 

If you want to use the IZAR CENTER device as M-Bus repeater, connect the 
M-Bus output of another IZAR CENTER to clamp 1 and 2. 

Modem, PC:

 

Connect a modem to connector 67. Use the interface cable provided with your 
modem (maximum cable length: 10 m). 

USB:

   

 

Maximum cable length 3 m. Use the provided USB cable. 

 
 

Display 

 
The IZAR CENTER device has got a total of 5 display lights: 
 

M-Bus: 

Indication for 0 ... 100 % M-Bus load (green), 100 ...130 % M-Bus load 
(yellow, warning) and overload (red). If the yellow LED is lit up the maximum 
M-Bus load is reached. Do not connect any more M-Bus devices. In this state 
the IZAR CENTER has still full functionality. The red light signals an M-Bus 
overload. An overload occurs if there are too many M-Bus devices connected 
to the bus or if the bus lines are shortened. In this case the IZAR CENTER 
switches the M-Bus for approx. 2 seconds off. After that the bus load is tested 
and the bus is switched off again if the overload condition remains.

 

Communication:

 

The IZAR CENTER has got four different input channels: USB, LAN, RS232, 
Repeater. A green lightning next to USB/LAN resp. RS232/Repeater shows 
an established USB resp. RS232 connection. A yellow lightning shows an 
established LAN resp. Repeater connection. A green lightning next to Rx/Tx 