Hydromatic HPGLX200 Installation And Service Manual Download Page 4

4

Heat Sensor and Seal 
Failure Connections:

If a HYDROMATIC control panel
is  used,  terminal  blocks  are 
provided for heat sensor and seal
failure  connections.  (See  Panel
Schematic.)  If  a  control  panel 
is  supplied  by  others,  it 
must  allow  heat  sensor  and  seal
failure terminations.

Installing  Sump  Level  Control
Float Controls:

In  either  simplex,  duplex  or
triplex  systems  the  lower  or 
turn-off  control  is  to  be  set  to
maintain  a  minimum  level  in  the
sump. This level shall be no more
than  3

1

4

"  from  the  top  of  the

motor  housing  down  to  the 
surface of the sewage.
The second, or turn-on control, is
set  above  the  lower  turn-off 
control.  The  exact  distance
between the two floats must be a
compromise  between  a  frequent
pumping  cycle  (10  starts  per  hr.
max.)  to  control  septicity,  solids
and  a  slower  cycle  for  energy
economy. This distance should be
determined  by  the  engineer  or
consulting engineer, depending on
the conditions of the application.
For  installation  of  Hydromatic
supplied  level  controls  refer  to
your  systems  installation  and 
service manual.

Starting the Pump:

To  start  the  pump,  perform  the
following steps in order:

WARNING:  Keep  hands  and
clothing  away  from  cutters 
and impeller!

1. If pump is 3 phase, the rotation

of  the  impeller  must  first  be
checked.  Lift  pump  from
sump, lay it down, and quickly
turn pump on and then off.
The  impeller  should  turn 
counterclockwise when viewed
from  the  suction.  If  rotation 
is  wrong,  turn  off  main 
breaker  and  interchange  any
two  line  leads  to  motor  to 
correct rotation.
If pump is piped-in permanently
and  inlet  cannot  be  observed,
rotation  will  have  to  be
checked  by  pump  operation
described later.
If  pump  is  single  phase,  no 
rotation check is necessary.

2. Run  water  into  sump  until

motor is covered.

3. Open 

gate 

valve 

in 

discharge line.

4. Turn  pump  on.  If  pump  runs

and sump liquid does not pump
down,  stop  pump  and  close
discharge gate valve. Then lift
pump  until  sealing  flange 
is  open  to  vent  off  trapped 
air.  Lower  pump,  open 
discharge  valve,  and  start  the
pump again.

5. If  pump  is  3  phase,  piped  in

permanently, and still does not
operate properly after venting,
rotation  is  wrong  and  can  be
reversed  by  interchanging  any
two line leads.

6. Level controls should be set in

accordance  with  “Installing
Sump  Level  Control  Float
Controls” above.

CAUTION:  Be  sure  ground
wire  in  connected  to  good
ground such as water pipe. This
is important for safety.

As  the  motors  are  oil  filled,  no
lubrication  or  other  maintenance
is required.
If the heat sensor and seal failure
are  hooked  up  properly,  no 
attention  is  necessary  as  long  as
the  seal  failure  indicator  light
doesn’t  come  on.  To  ensure 
continuity  of  the  seal  sensor
leads,  a  test  light  is  provided  on
intrinsically safe HYDROMATIC
panels as standard equipment.
Pump  should  be  checked  every
quarter for corrosion and wear.

Servicing Instructions:

IMPORTANT: 

Read 

all 

directions  before  replacing 
any parts.

WARNING:  Before  handling
these  pumps  and  controls,
always 

disconnect 

the 

power first.

Do not smoke or use sparkable
electrical devices or flames in a
septic  (gaseous)  or possible 
septic sump.

Field  Service  on  HYDROMATIC
Explosion Proof Pumps: 

If  a  HYDROMATIC  explosion
proof  pump  is  used  in  a  hazardous
location, or if the pump is still in
warranty,  the  pump  must  be
returned to the factory for service
or  repaired  in  an  authorized
HYDROMATIC  service  center.
This  will  ensure  the  integrity  of
the  hazardous  location  rating  of
the  pump  and  comply  with  our
warranty  requirements.  Pumps
out of warranty and not used in a
hazardous  location  can  be  field

Pump

Operations

Pump

Maintenance

Summary of Contents for HPGLX200

Page 1: ...ure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the system Explosion Proof Submersible Grinder Pumps Class I Division 1 Group C D FM HPGX200...

Page 2: ...ble concealed shipping damage Any damage should be reported immediately to delivery carrier Claims for damage must originate at the receiving end Claims for shipping damage cannot be processed at the...

Page 3: ...for use in making the installation All wires should be checked for shorts to ground with an ohmmeter or Meggar after the connections are made This is important as one grounded wire can cause considera...

Page 4: ...s necessary 2 Run water into sump until motor is covered 3 Open gate valve in discharge line 4 Turn pump on If pump runs and sump liquid does not pump down stop pump and close discharge gate valve The...

Page 5: ...rts can now be cleaned without removing them from the shaft 7 If necessary to replace cutters remove hex head screw 19 washer 20 and radial cutter 40 from shaft Radial cutter 40 and impeller 17 are sc...

Page 6: ...e wire connections and then remove the power cable 4 Turn the motor housing over and remove the stator bolts 29 from the stator 31 then remove the stator from the motor housing 33 5 Place new stator 3...

Page 7: ...or piping plugged 4 Wrong rotation 5 Speed too low Insufficient liquid delivered 1 Discharge head too high 2 Impeller or cutters partially plugged or damaged 3 Wrong rotation 4 Incorrect diameter imp...

Page 8: ...Stator 2HP 230 1 60 1 10832 203 1 Stator 2HP 200 1 60 1 32 10823 101 5 Rotor Shaft Assy 2HP 3f 1 10832 101 5 Rotor Shaft Assy 2HP 1f 1 33 13494 004 2 Motor Housing 1 34 00065 001 1 Upper Bearing R 1...

Page 9: ...4 14 15 15 13 13 26 26 28 28 16 16 39 39 18 18 17 17 42 42 40 40 41 41 19 19 20 20 27 27 22 22 7 21 21 6 24 24 25 25 23 23 11 11 12 12 9 10 10 5 3 4 1 38 38 36 36 29 29 32 32 30 30 31 31 34 34 35 35 3...

Page 10: ...or 2HP 200 3 60 1 10823 603 1 Stator 2HP 575 3 60 1 10832 003 1 Stator 2HP 230 1 60 1 10832 203 1 Stator 2HP 200 1 60 1 32 10823 101 5 Rotor Shaft Assy 2HP 3f 1 10832 101 5 Rotor Shaft Assy 2HP 1f 1 3...

Page 11: ...15 13 13 26 26 28 28 16 16 39 39 18 18 17 17 42 42 40 40 41 41 19 19 20 20 27 27 22 22 7 21 21 6 24 24 25 25 23 23 11 11 12 12 9 10 10 5 3 4 1 38 38 36 36 29 29 32 32 30 30 31 31 34 34 35 35 33 33 2 3...

Page 12: ...on Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that does not c...

Reviews: