HNS 526
7
Version: 06.10.2014
HYDAC
ELECTRONIC
GMBH
Part No.: 669869
E
4 Installation
To ensure safe operation of the level sensor the following conditions must be met:
■
The sensor must only be used in non-pressurized applications.
■
The sensor must be mounted vertically to the fluid surface.
■
Ensure that no obstacles project into the blind zone.
■
Ensure that there are no components (e.g. threaded connections, hoses, inlet pipes etc.)
inside the ultrasound field.
■
Prevent adhesions (e.g. drops of water, contaminants) from collecting on the sensor
head.
Blind zone
90°
Recom
m
ended
applicat
ion r
ange
Hoses/
pipes