Elektronischer Druckschalter 
Electronic Pressure Switch 
Manocontacteur électronique 

EDS 3000 

Mit IO-Link Schnittstelle 

With IO-Link Interface 

Avec interface IO-Link 

Mat –Nr. 6

69897

 / Stand: 04.02.2

016 D/E/F

 

Summary of Contents for EDS 3000

Page 1: ... of original instructions Notice d utilisation traduction de l original Elektronischer Druckschalter Electronic Pressure Switch Manocontacteur électronique EDS 3000 Mit IO Link Schnittstelle With IO Link Interface Avec interface IO Link Mat Nr 669897 Stand 04 02 2016 D E F ...

Page 2: ...0 1 1 Twopoint mode Einstellung auf Schaltpunkt SP 11 10 1 2 Window mode Einstellung auf Fensterfunktion Fno Fnc 12 10 2 EINSTELLBEREICHE FÜR DIE SCHALTAUSGÄNGE 13 10 3 ANALOGAUSGANG 13 11 Grundeinstellungen 14 11 1 HAUPTMENÜ 14 11 2 ERWEITERTE FUNKTIONEN 15 12 Ändern der Grundeinstellungen 16 13 Rücksetzen des Spitzenwertes 17 14 Programmierfreigabe 17 14 1 ÄNDERN DER PROGRAMMIERFREIGABE 17 15 Nu...

Page 3: ...ngaben 23 19 1 EDS 3000 MIT KERAMIK SENSORZELLE ABSOLUT UND RELATIVDRUCK BIS 16 BAR 500 PSI 23 19 2 EDS 3000 MIT DÜNNFILM DMS SENSORZELLE RELATIVDRUCK AB 40 BAR 1000 PSI 24 20 Zubehör 25 20 1 FÜR DEN ELEKTRISCHEN ANSCHLUSS 25 20 2 FÜR DEN MECHANISCHEN ANSCHLUSS 25 21 Geräteabmessung 27 ...

Page 4: ...gbar sein Bitte beachten Sie dass die in dieser Dokumentation gemachten Angaben der Gerätetechnik zu dem Zeitpunkt der Literaturerstellung entsprechen Abweichungen bei technischen Angaben Abbildungen und Maßen sind deshalb möglich Entdecken Sie beim Lesen dieser Dokumentation Fehler oder haben weitere Anregungen und Hinweise so wenden Sie sich bitte an HYDAC ELECTRONIC GMBH Technische Dokumentatio...

Page 5: ...etzung von Leben Körper und Gesundheit Sofern wir fahrlässig eine vertragswesentliche Pflicht verletzen ist unsere Haftung auf den vorhersehbaren Schaden begrenzt Ansprüche aus Produkthaftung bleiben unberührt Im Falle der Übersetzung ist der Text der deutschen Originalbedienungsanleitung der allein gültige 3 Funktionen des EDS 3000 Je nach Ausführung bietet das Gerät folgende Funktionen Unterstüt...

Page 6: ...n reduzieren Möglichst kurze Leitungsverbindungen herstellen Leitungen mit Schirm verwenden z B LIYCY 4 x 0 5 mm Der Kabelschirm ist in Abhängigkeit der Umgebungsbedingungen fachmännisch und zum Zweck der Störunterdrückung einzusetzen Direkte Nähe zu Verbindungsleitungen von Leistungsverbrauchern oder störenden Elektro oder Elektronikgeräten ist möglichst zu vermeiden 5 Bedienelemente des EDS 3000...

Page 7: ...swerte auszulesen Die Mittel LED blinkt 7 Parametrierung Der Druckschalter kann über die Tasten am Gerät oder über die IO Link Schnittstelle mit jedem IO Link fähigen Master Konfigurationstool gemäß IO Spezifikation V1 1 parametriert werden Die IO Link Spezifikation V1 0 wird ebenfalls unterstützt Wird der eingelesene Parametersatz vom Gerät nicht akzeptiert empfehlen wir den Parametersatz auf Pla...

Page 8: ...usgang und 1 Analogausgang Er kann mit dem HYDAC Programmiergerät HPG P1 000 oder dem HYDAC Programmieradapter ZBE P1 000 flexibel an die jeweilige Applikation angepasst werden 8 1 PROGRAMMIERUNG MIT HPG P1 000 Anschluss mit Standardkabel Device 1 HPG P1 2 3 4 5 1 2 3 4 5 Ub 0 V 1 2 3 4 Ub 0 V Q1 C 8 2 PROGRAMMIERUNG MIT ZBE P1 000 Anschluss mit Standardkabel Device 1 ZBE P1 2 3 4 5 1 2 3 4 5 L L ...

Page 9: ...Ausgang 2 fk2 FH2 Druckfenster unterer Wert Ausgang 2 fl2 FL2 Erweiterte Funktionen ef EF Rücksetzen res RES Schaltverzögerungszeit Ausgang 1 ds1 dS1 Schaltverzögerungszeit Ausgang 2 ds2 dS2 Rückschaltverzögerungszeit Ausgang 1 dr1 dR1 Rückschaltverzögerungszeit Ausgang 2 dr2 dR2 Ausgang 1 ov1 Ou1 Ausgang 2 ov2 Ou2 Stromausgang i I Spannungsausgang v U Schließer bei Hysteresefunktion kno HNO Schli...

Page 10: ... Yes Nein no No Reset Max Wert rS kL rS HL Programmiersperre Pr6 PrG Nullpunktkalibrierung CALi cALi Neu nEU nEU HINWEISE Übersteigt der aktuelle Druck den Nenndruck des Gerätes so kann er nicht mehr angezeigt werden und die Anzeige beginnt zu blinken Liegt der aktuelle Druck unterhalb 0 6 des Nennbereiches so wird 0 bar angezeigt ...

Page 11: ...imitierung auf die jeweilige Messbereichsober bzw untergrenze 10 1 1 Twopoint mode Einstellung auf Schaltpunkt SP Zu jedem Schaltausgang kann ein Schaltpunkt und ein Rückschaltpunkt eingestellt werden Der jeweilige Ausgang schaltet wenn der eingestellte Schaltpunkt erreicht wurde und schaltet zurück wenn der Rückschaltpunkt unterschritten wurde Beispiel für Schaltpunkt 1 Öffner und Schließerfunkti...

Page 12: ...erfolgen Beispiel für Schaltausgang 1 Öffner und Schließerfunktion Abkürzungen FH1 FH2 oberer Schaltwert 1 bzw 2 FL1 FL2 unterer Schaltwert 1 bzw 2 FNO Schließer bei Fensterfunktion FNC Öffner bei Fensterfunktion HINWEISE Eine Einstellung des oberen Schaltwertes FH ist nur möglich wenn er oberhalb des zugehörigen unteren Schaltwertes FL liegt Die Fensterfunktion arbeitet nur dann ordnungsgemäß Ein...

Page 13: ... 5 0 400 4 400 4 1 0 600 6 600 6 1 Alle in der Tabelle angegebenen Bereiche sind im Raster der Schrittweite einstellbar Messbereich Untere Grenze von RP FL Obere Grenze von SP FH Mindestabstand zw RP und SP bzw FL und FH Schrittweite in psi in psi in psi in psi 0 15 0 15 15 0 15 0 05 0 30 0 30 30 0 3 0 05 0 50 0 5 50 0 5 0 1 14 75 13 0 75 1 0 0 2 0 150 1 5 150 1 5 0 5 0 250 2 5 250 2 5 0 5 0 500 5...

Page 14: ...instellungen Zur Anpassung an die jeweilige Applikation kann das Verhalten des EDS 3000 über mehrere Einstellungen verändert werden Diese sind zu einem Menü zusammengefasst 11 1 HAUPTMENÜ Der Bereich wird nicht angezeigt wenn in Erweiterte Funktionen unter ou2 i oder u eingestellt ist ...

Page 15: ...EDS 3000 IO Link 15 Stand 04 02 2016 HYDAC ELECTRONIC GMBH Mat Nr 669897 D 11 2 ERWEITERTE FUNKTIONEN Der Bereich wird nicht angezeigt wenn in Erweiterte Funktionen unter ou2 i oder u eingestellt ist ...

Page 16: ... Mat Nr 669897 D 12 Ändern der Grundeinstellungen HINWEIS Bei aktiviertem Menü werden keine Schaltfunktionen ausgeführt HINWEIS Erfolgt ca 60 Sekunden lang keine Tastenbetätigung wird das Menü automatisch beendet ohne dass eventuelle Änderungen wirksam werden ...

Page 17: ...grammierung frei FREE und Programmierung gesperrt Loc entschieden werden mit bzw erfolgt der Wechsel zwischen den Möglichkeiten Einstellung mit der mode Taste quittieren 15 Nullpunktkalibrierung Die Funktion Cali ermöglicht eine Nullpunktkallibrierung Der momentane Druck wird als neuer Nullpunkt gespeichert Dies ist im Bereich 3 des Gerätenenndruckes möglich In den Erweiterten Funktionen die Taste...

Page 18: ...be E 12 Bei den abgespeicherten Kalibrierdaten wurde ein Fehler erkannt Mögliche Ursachen sind starke elektromagnetische Störungen oder ein Bauteildefekt Abhilfe Gerät von der Versorgungsspannung trennen und wieder verbinden Steht der Fehler weiter an muss das Gerät zur Neukalibrierung oder Reparatur ins Werk zurück E 21 Es wurde ein Kommunikationsfehler innerhalb des Gerätes erkannt Mögliche Ursa...

Page 19: ...Sensorzelle Keramik Dichtung FPM EPDM gemäß Typenschlüssel Ausgangsgrößen Ausgangssignale Ausgang 1 Schaltausgang Ausgang 2 konfigurierbar als Schaltausgang oder Analogausgang Schaltausgang PNP Transistorschaltausgänge Schaltstrom SP1 max 0 1 A SP2 max 0 25 A Schaltzyklen 100 Millionen Analogausgang zulässige Bürde wählbar 4 20 mA Bürde max 500 Ω 0 10 V Bürde min 1 kΩ Genauigkeit nach DIN 16086 Gr...

Page 20: ...eristic 0x0001 Device Profile Smart Sensor 0x8000 Function Class Device Identification 0x8001 Function Class Binary Data Channel 0x8002 Function Class Process Data Variables Supported Access Locks Parameter Data Storage Local Parameterization Local User Interface Communication IO Link Revision V1 1 Unterstützung V1 0 Transmission Rate Baudrate 38 4 kBaud COM2 Minimum Cycle Time 2 5 ms Prozessdaten...

Page 21: ...unkteinstellung 0 5 FS typ 1 FS max Temperaturdrift Typ Nullpunkt Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Temperaturdrift Typ Spanne Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Wiederholbarkeit 0 25 FS max Reaktionszeit 10 ms Langzeitdrift 0 3 FS typ Jahr Umgebungsbedingungen Kompensierter Temperaturbereich 10 70 C 14 158º F Betriebstemperaturbereich 25 80 C 13 176º F Lagertemperatur...

Page 22: ...rization Local User Interface Communication IO Link Revision V1 1 Unterstützung V1 0 Transmission Rate Baudrate 38 4 kBaud COM2 Minimum Cycle Time 2 5 ms Prozessdatenbreite 16 Bit SIO Mode Supported Yes M Sequence Capability PREOPERATE TYPE_0 OPERATE TYPE_2_2 ISDU supported Verbindung mit ungeschirmter Standard Sensorleitung bis zu einer maximalen Leitungslänge von 20 m möglich Download der IO Dev...

Page 23: ... Druckbereich in psi 9 Einschraubloch DIN 3852 G1 4 nur in Verbindung mit Druckbereich in bar Anschlussart elektrisch 6 Gerätestecker M12x1 4 pol ohne Kupplungsdose Ausgang F31 IO Link Schnittstelle Druckbereich Ausführung 1 Keramik absolut In bar 0001 02 5 In psi 0015 0050 Ausführung 3 Keramik relativ In bar 0001 1 1 bar 01 0 02 5 06 0 0010 0016 In psi 0015 0030 0050 0150 0250 0500 0089 14 75 psi...

Page 24: ...4 A ISO 1179 2 DIN 3852 nur in Verbindung mit Druckbereich in bar 7 9 16 18 UNF 2A SAE6 Außengewinde nur in Verbindung mit Druckbereich in psi 9 Einschraubloch DIN 3852 G1 4 nur in Verbindung mit Druckbereich in bar Anschlussart elektrisch 6 Gerätestecker M12x1 4 pol ohne Kupplungsdose Ausgang F31 IO Link Schnittstelle Druckbereich In bar 0040 0100 0250 0400 0600 In psi 1000 3000 6000 9000 Modifik...

Page 25: ...2 4 pol Kupplungsdose abgewinkelt mit 2 m Leitung Material Nr 6006790 ZBE 06 05 4 pol Kupplungsdose abgewinkelt mit 5 m Leitung Material Nr 6006789 Farbkennung Pin 1 braun Pin 2 weiß Pin 3 blau Pin 4 schwarz 20 2 FÜR DEN MECHANISCHEN ANSCHLUSS ZBM 3000 Schelle zur Wandbefestigung anschraubbar Werkstoff Unterteil TPE Santoprene 10187 Oberteil Bandstahl DIN 95381 1 4571 Material Nr 3184630 ...

Page 26: ...Schelle zur Wandbefestigung anschweißbar Werkstoff Schweißlasche QSTE340TM galvanischer Überzug EN 12329 FE ZN8 B Unterteil TPE Santoprene 10187 Oberteil Bandstahl DIN 95381 1 4571 Material Nr 3184632 ZBM 3200 Spritzwasserschutz Werkstoff Elastollan S60 A15 SPF 000 Material Nr 3201919 ...

Page 27: ...EDS 3000 IO Link 27 Stand 04 02 2016 HYDAC ELECTRONIC GMBH Mat Nr 669897 D 21 Geräteabmessung ...

Page 28: ...er HYDAC Service zur Verfügung HYDAC SERVICE GMBH Hauptstr 27 D 66128 Saarbrücken Germany Tel 49 0 6897 509 1936 Fax 49 0 6897 509 1933 Anmerkung Die Angaben in dieser Bedienungsanleitung beziehen sich auf die beschriebenen Betriebsbedingungen und Einsatzfälle Bei abweichenden Einsatzfällen und oder Betriebsbedingungen wenden Sie sich bitte an die entsprechende Fachabteilung Bei technischen Fragen...

Page 29: ...Operating Instructions Translation of original instructions Electronic Pressure Switch EDS 3000 With IO Link Interface Part no 669897 Edition 2016 02 04 E ...

Page 30: ...G OUTPUTS 11 10 1 1 Twopoint mode Switch point setting SP 11 10 1 2 Window mode Window function setting Fno Fnc 12 10 2 SETTING RANGES FOR THE SWITCHING OUTPUTS 13 10 3 ANALOGUE OUTPUT 13 11 Basic Settings 14 11 1 MAIN MENU 14 11 2 EXTENDED FUNCTIONS 15 12 Changing the Basic Settings 16 13 Resetting the peak value 17 14 Program enable 17 14 1 CHANGING THE PROGRAM ENABLE 17 15 Zero point calibratio...

Page 31: ... 23 19 1 EDS 3000 WITH CERAMIC SENSOR CELL ABSOLUTE AND RELATIVE PRESSURE UP TO 16 BAR 500 PSI 23 19 2 EDS 3000 WITH THIN FILM DMS SENSOR CELL RELATIVE PRESSURE STARTING AT 40 BAR 1000 PSI 24 20 Accessories 25 20 1 FOR ELECTRICAL CONNECTION 25 20 2 FOR MECHANICAL CONNECTION 25 21 Dimensions 27 ...

Page 32: ...iate reference Please note the specifications given in this documentation regarding the instrument technology were correct at the time of publishing Modifications to technical specifications illustrations and dimensions are therefore possible If you discover errors while reading the documentation or have additional suggestions or tips please contact us at HYDAC ELECTRONIC GMBH Technical Documentat...

Page 33: ...lth If we negligently breach any material contractual obligation our liability shall be limited to foreseeable damage Claims due to the Product Liability shall remain unaffected In the event of translation only the original version of the operating manual in German is legally valid 3 Functions of the EDS 3000 Depending on the model the instrument has the following functions Supports IO Link specif...

Page 34: ...rference Make line connections as short as possible Use shielded lines e g LIYCY 4 x 0 5 mm The cable screening must be fitted by qualified personnel subject to the ambient conditions and with the aim of suppressing interference Keep the unit well away from the electrical supply lines of power equipment as well as from any electrical or electronic equipment causing interference 5 Control elements ...

Page 35: ...ead out measured values The centre LED flashes 7 Parameterisation The pressure switch can be parameterised via the device keys or via the IO Link interface by means of any IO Link compatible master configuration tool according IO specifications V1 1 Supports IO Link specifications V1 0 Should the read parameter sets from the device not be accepted we recommend to carry out a plausibility check of ...

Page 36: ...ut and 1 analogue output It can be flexibly adapted to the related application by means of the HYDAC programming device HPG P1 000 or the HYDAC programming adapter ZBE P1 000 8 1 PROGRAMMING WITH HPG P1 000 Connection with standard cable Device 1 HPG P1 2 3 4 5 1 2 3 4 5 Ub 0 V 1 2 3 4 Ub 0 V Q1 C 8 2 PROGRAMMING WITH ZBE P1 000 Connection with standard cable Device 1 ZBE P1 2 3 4 5 1 2 3 4 5 L L ...

Page 37: ...2 FH2 Pressure window lower value output 2 FL2 FL2 Extended functions ef EF Reset to factory defaults res RES Switch delay time output 1 ds1 dS1 Switch delay time output 2 ds2 dS2 Switch back delay time output 1 dr1 dR1 Switch back delay time output 2 dr2 dR2 Output 1 ov1 Ou1 Output 2 ov2 Ou2 Current output i I Voltage output v U N O when hysteresis function is active kno HNO N O when window funct...

Page 38: ...o No No Reset max value rS kL rS HL Programming lock Pr6 PrG Zero point calibration CALi cALi New nEU nEU NOTES If the current pressure exceeds the device s nominal pressure it can no longer be displayed and the display begins to flash If the actual pressure is less than 0 6 of the nominal range 0 bar is displayed ...

Page 39: ...measuring range 10 1 1 Twopoint mode Switch point setting SP One switch point and one switch back point can be set for each switching output The particular output will switch when the pre set switch point is reached and then switch back when the level drops below the switch back point Example for switch point 1 N C and N O function Abbreviations SP1 SP2 switch point 1 switch point 2 RP1 RP2 switch...

Page 40: ...ch value 1 upper switch value 2 FL1 FL2 lower switch value 1 lower switch value 2 FNO N O when window function is active FNC N C when window function is active NOTES Setting the upper switch value FH is only possible if it lies above the lower switch value FL The window function only works properly switching on and off if all switch values including the safety margin are greater than 0 bar offset ...

Page 41: ... 2 5 250 0 2 5 0 5 0 400 4 400 4 1 0 600 6 600 6 1 All ranges shown in the table can be adjusted by the increments shown Measuring range Untere Grenze von RP FL Upper limit of SP FH Minimum difference betw RP and SP or FL and FH Increment in psi in psi in psi in psi 0 15 0 15 15 0 15 0 05 0 30 0 30 30 0 3 0 05 0 50 0 5 50 0 5 0 1 14 75 13 0 75 1 0 0 2 0 150 1 5 150 1 5 0 5 0 250 2 5 250 2 5 0 5 0 ...

Page 42: ... 11 Basic Settings The EDS 3000 can be adapted to suit the particular application as required by changing multiple settings These settings are combined in a menu 11 1 MAIN MENU The range is not displayed if i or u is pre set under ou2 in the extended functions Extended functions ...

Page 43: ...EDS 3000 IO Link 15 Edition 2016 02 04 HYDAC ELECTRONIC GMBH Part No 669897 E 11 2 EXTENDED FUNCTIONS The range is not displayed if i or u is pre set under ou2 in the extended functions ...

Page 44: ... 669897 E 12 Changing the Basic Settings NOTICE When the menu is activated no switching operations are carried out NOTICE If there has been no activity in this menu for approx 60 seconds the menu will automatically close and any changes you have made will not be applied ...

Page 45: ...programming Loc By pressing or you can switch between these options Confirm by pressing the mode key 15 Zero point calibration The function Cali enables the calibration of the sensor zero point The current pressure is saved as the new zero point This is possible in the range 3 of the instrument rated pressure In the extended functions menu please press the key until Cali appears Press the mode key...

Page 46: ...E 12 An error was detected in the saved calibration data Possible causes are strong electromagnetic interference or a defective component Action Disconnect then reconnect the supply voltage to the instrument If the error persists the instrument must be returned to the factory for recalibration or repair E 21 A communication error within the unit has been detected Possible causes are strong electro...

Page 47: ...tainless steel Sensor cell Ceramic Seal FPM EPDM as per model code Output data Output signals Output 1 switching output Output 2 can be configured as switching output or as analogue output Switch outputs PNP transistor switching outputs Switching current SP1 max 0 1 A SP2 max 0 25 A Switching cycles 100 million Analogue output permitted load resistance selectable 4 20 mA load resistance max 500 Ω ...

Page 48: ...torage Yes Profile Characteristic 0x0001 Device Profile Smart Sensor 0x8000 Function Class Device Identification 0x8001 Function Class Binary Data Channel 0x8002 Function Class Process Data Variables Supported Access Locks Parameters Data Storage Local Parameterisation Local User Interface Communication IO Link Revision V1 1 support V1 0 Transmission Rate Baud Rate 38 4 kBaud COM2 Minimum Cycle Ti...

Page 49: ...curacy to DIN 16086 Max setting 0 5 FS typ 1 FS max Temperature drift Typ zero point Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Temperature drift Typ range Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Repeatability 0 25 FS max Reaction time 10 ms Long term drift 0 3 FS typ year Environmental conditions Compensated temperature range 10 70 C 14 158º F Operating temperature range 25 80 C 13...

Page 50: ...orage Local Parameterisation Local User Interface Communication IO Link Revision V1 1 support V1 0 Transmission Rate Baud Rate 38 4 kBaud COM2 Minimum Cycle Time 2 5 ms Process data width 16 Bit SIO Mode Supported Yes M Sequence Capability PREOPERATE TYPE_0 OPERATE TYPE_2_2 ISDU supported Connection with unscreened standard sensor line possible up to a max line length of 20 m Download the IO Devic...

Page 51: ... ranges in psi 9 Threaded port DIN 3852 G1 4 only in conjunction with pressure ranges in bar Electrical connection 6 Male M12x1 4 pole connector not supplied Output F31 IO Link interface Pressure ranges in bar Type 1 ceramic absolute In bar 0001 02 5 In psi 0015 0050 Type 3 ceramic relative In bar 0001 1 1 bar 01 0 02 5 06 0 0010 0016 In psi 0015 0030 0050 0150 0250 0500 0089 14 75 psi Modificatio...

Page 52: ... 1179 2 DIN 3852 male thread only in conjunction with pressure ranges in bar 7 9 16 18 UNF 2A SAE6 male thread only in conjunction with pressure ranges in psi 9 Threaded port DIN 3852 G1 4 only in conjunction with pressure ranges in bar Electrical connection 6 Male M12x1 4 pole connector not supplied Output F31 IO Link interface Pressure ranges in bar In bar 0040 0100 0250 0400 0600 In psi 1000 30...

Page 53: ... Female connector right angle with 2 m cable Part No 6006790 ZBE 06 05 4 pole Female connector right angle with 5 m cable Part No 6006789 Colour coding Pin 1 brown Pin 2 white Pin 3 blue Pin 4 black 20 2 FOR MECHANICAL CONNECTION ZBM 3000 Clamp for wall mounting screw type fitting Material of lower section TPE Santoprene 10187 Material of top section Steel strip DIN 95381 1 4571 Material No 318463...

Page 54: ... wall mounting weld type fitting Material of welding bridge QSTE340TM zinc coating EN 12329 FE ZN8 B Material of lower section TPE Santoprene 10187 Material of top section Steel strip DIN 95381 1 4571 Material No 3184632 ZBM 3200 Splash guard Material Elastollan S60 A15 SPF 000 Material No 3201919 ...

Page 55: ...EDS 3000 IO Link 27 Edition 2016 02 04 HYDAC ELECTRONIC GMBH Part No 669897 E 21 Dimensions connector M12x1 4 pole FPM EPDM seal 6hex SW27 Diameter Display adjustable 270 Housing adjustable 340 ...

Page 56: ...act HYDAC Service HYDAC SERVICE GMBH Hauptstr 27 D 66128 Saarbruecken Germany Tel 49 0 6897 509 1936 Fax 49 0 6897 509 1933 Note The information in this manual relates to the operating conditions and applications described For applications and operating conditions not described please contact the relevant technical department If you have any questions suggestions or encounter any problems of a tec...

Page 57: ...Notice d utilisation traduction de l original Manocontacteur électronique EDS 3000 Avec interface IO Link Code art 669897 Edition 04 02 2016 F ...

Page 58: ...Twopoint mode Réglage du seuil d enclenchement SP 11 10 1 2 Fonction fenêtre Réglage fonction fenêtre Fno Fnc 12 10 2 RÉGLAGE DES SORTIES DE COMMUTATION 13 10 3 SORTIE ANALOGIQUE 13 11 Menu de base 14 11 1 MENU PRINCIPAL 14 11 2 FONCTIONS COMPLEMENTAIRES 15 12 Modifications dans le menu de base 16 13 Réinitialiser la valeur supérieure 17 14 Activation de la programmation 17 14 1 MODIFICATION DE L ...

Page 59: ...23 19 1 EDS 3000 AVEC CELLULE CERAMIQUE PRESSION ABSOLUE ET RELATIVE JUSQU A 16 BAR 500 PSI 23 19 2 EDS 3000 AVEC CELLULE COUCHE MINCE PRESSION RELATIVE A PARTIR DE 40 BAR 1000 PSI 24 20 Accessoires 25 20 1 POUR LE RACCORDEMENT ELECTRIQUE 25 20 2 POUR LE RACCORDEMENT MECANIQUE 25 21 Encombrements 27 ...

Page 60: ...ilisation Veuillez noter que les informations fournies dans cette documentation correspondent à la technique de l appareil au moment de l élaboration de ce document Pour cette raison les différentes données techniques illustrations et mesures sont susceptibles de diverger Si lors de la lecture de cette documentation vous deviez détecter des erreurs ou encore si vous aviez des suggestions ou des re...

Page 61: ... atteinte fautive à la vie à l intégrité corporelle ou à la santé En cas de violation par négligence d une obligation fondamentale du contrat notre responsabilité est limitée au dommage prévisible Cette limitation de la responsabilité ne concerne pas la responsabilité légales des produits En cas de traduction le texte de la version originale en allemand est le seul valable 3 Fonctions de l EDS 300...

Page 62: ...lectromagnétiques Utiliser les liaisons câblées les plus courts possibles Utiliser des câbles blindés p ex LIYCY 4 x 0 5 mm Le câble blindé est à mettre en œuvre en fonction des conditions environnantes par des spécialistes afin de diminuer les perturbations électromagnétiques Eviter si possible de placer l appareil à proximité d appareils électriques ou électroniques générateurs de perturbations ...

Page 63: ...our la lecture des valeurs de mesure L indicateur LED du milieu clignote 7 Paramétrage Vous pouvez parametrer le manocontacteur électronique à l aide de chaque outil de configuration IO Link par le biais des touches ou via l interface IO Link selon spécifications IO V1 1 Soutient également les spécifications IO Link V1 0 Si le jeu de paramètres enregistrés n est pas valable il est recommandé de vé...

Page 64: ...ortie analogique Vous pouvez souplement l adapter à l application respective à l aide de l appareil de programmation HYDAC HPG P1 000 ou à l aide de l adaptateur de programmation HYDAC ZBE P1 000 8 1 PROGRAMMATION A L AIDE DE L HPG P1 000 raccordement câble standard Device 1 HPG P1 2 3 4 5 1 2 3 4 5 Ub 0 V 1 2 3 4 Ub 0 V Q1 C 8 2 1 1 PROGRAMMATION A L AIDE DU ZBE P1 000 raccordement câble standard...

Page 65: ... supérieure Sortie 2 fk2 FH2 Fenêtre de pression valeur inférieure Sortie 2 FL2 FL2 Fonctions complémentaires EF EF RAZ res RES Temporisation à l enclenchement Sortie 1 ds1 dS1 Temporisation à l enclenchement Sortie 2 ds2 dS2 Temporisation au déclenchement sortie 1 dr1 dR1 Temporisation au déclenchement sortie 2 dr2 dR2 Sortie 1 ov1 Ou1 Sortie 2 ov2 Ou2 Sortie de courant i I Sortie de tension v U ...

Page 66: ...s Yes Non no No RAZ valeur max rS kL rS HL Verrou de programmation Pr6 PrG Calibrage du point zéro CALi cALi Nouveau nEU nEU REMARQUES Si la pression actuelle dépasse la pression nominale de l appareil alors celle ci ne peut plus être affichée et l affichage clignote Si la pression actuelle se trouve en dessous de 0 6 de la zone nominale l appareil affiche 0 bar ...

Page 67: ...e inférieure ou supérieure de la plage de mesure respective 10 1 1 Twopoint mode Réglage du seuil d enclenchement SP Pour chaque sortie de commutation il est possible de régler un seuil d enclenchement et de déclenchement La sortie concernée commute lorsqu on a atteint le seuil d enclenchement et se décommute lorsqu on est en dessous du seuil de déclenchement Exemple pour point de commutation 1 fo...

Page 68: ...e de sécurité qui permet d éviter les commutations intempestives Exemple pour sortie de commutation 1 fonction ouvrante et fermante Raccourcis FH1 FH2 valeur de commutation supérieure 1 ou 2 FL1 FL2 valeur de commutation inférieure 1 ou 2 FNO fonction fermante avec fonction fenêtre FNC fonction ouvrante avec fonction fenêtre REMARQUES Un réglage propre de la valeur d enclenchement supérieure FH es...

Page 69: ... 1 0 100 0 1 0 0 2 0 250 2 5 250 0 2 5 0 5 0 400 4 400 4 1 0 600 6 600 6 1 Toutes les plages indiquées dans le tableau sont réglables en fonction du pas indiqué Plage de mesure Seuil inférieur de RP FL Seuil supérieur de SP FH Distance minimum entre RP et SP ou FL et FH Pas en psi en psi en psi en psi 0 15 0 15 15 0 15 0 05 0 30 0 30 30 0 3 0 05 0 50 0 5 50 0 5 0 1 14 75 13 0 75 1 0 0 2 0 150 1 5 ...

Page 70: ...s adapter à chaque application le fonctionnement de l EDS 3000 peut être modifié à l aide de plusieurs réglages de base Ceux ci sont regroupés dans un menu 11 1 MENU PRINCIPAL La zone n est pas affichée si i ou u est réglé dans le point de menu fonctions complémentaires sous ou2 Fonctions complémentaires ...

Page 71: ...00 IO Link 15 Edition 04 02 2016 HYDAC ELECTRONIC GMBH Code art 669897 F 11 2 FONCTIONS COMPLEMENTAIRES La zone n est pas affichée si i ou u est réglé dans le point de menu fonctions complémentaires sous ou2 ...

Page 72: ...897 F 12 Modifications dans le menu de base REMARQUE En activant ce menu les fonctions de commutations sont désactivées REMARQUE Si au bout de 60 secondes aucune touche n a été appuyée l affichage retourne à son état de fonctionnement normal sans sauvegarde des modifications ...

Page 73: ...e Ici vous pouvez sélectionner programmation autorisée FREE ou programmation verrouillée En appuyant ou vous pouvez passer d une option à l autre Confirmer le réglage à l aide de la touche mode 15 Calibrage du point zéro La fonction Cali permet un tarage zéro du capteur La pression momentanée est enregistrée comme nouveau point zéro Cela est possible dans la plage 3 de la pression nominale de l ap...

Page 74: ...rs de la sauvegarde des données de calibrage une erreur a été détectée Les sources de pannes peuvent être de fortes perturbations électromagnétiques ou un défaut de construction Remède Débrancher puis rebrancher la tension d alimentation Si l erreur subsiste l appareil doit être recalibré ou réparé en usine E 21 Une erreur de communication a été détectée Les sources de pannes peuvent être de forte...

Page 75: ...le Cellule de mesure céramique Joint FPM EPDM selon code de commande Valeurs de sortie Signaux de sortie Sortie 1 sortie de commutation Sortie 2 configurable comme sortie de commutation ou sortie analogique Sortie de commutation PNP sortie de commutation transistor Courant de commutation SP1 max 0 1 A SP2 max 0 25 A Cycles de commutation 100 millions Sortie analogique charge autorisée Sélectionnab...

Page 76: ...IO Link Caractéristiques Paramètres Yes Stockage des données Yes Profiles characteristiques 0x0001 Device Profile Smart Sensor 0x8000 Function Class Device Identification 0x8001 Function Class Binary Data Channel 0x8002 Function Class Process Data Variables Supported Access Locks Paramètres Stockage des données Paramétrage locale Interface utilisateur local Communication Révision IO Link V1 1 assi...

Page 77: ... Typ point zéro Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Dérive en température Typ étendue Max 0 015 FS C 0 0085 FS F 0 025 FS C 0 014 FS F Reproductibilité 0 25 FS max Temps de réaction 10 ms Dérive dans le temps 0 3 FS typ an Conditions environnementales Plage de température compensée 10 70 C 14 158º F Plage de température de service 25 80 C 13 176º F Plage de températures de stockage 40...

Page 78: ...ocale Interface utilisateur local Communication Révision IO Link V1 1 assistance V1 0 Transmission Rate Baudrate 38 4 kBaud COM2 Minimum Cycle Time 2 5 ms Etendue des données de process 16 Bit SIO Mode Supported Yes M Sequence Capability PREOPERATE TYPE_0 OPERATE TYPE_2_2 ISDU supported Connexion avec une ligne capteur standard non blindée jusqu à une longueur de max 20 m possible Téléchargement d...

Page 79: ...ice taraudé DIN 3852 G1 4 avec plage de pression en bar Raccordement électrique 6 Embase M12X1 4 pôles livré sans connecteur Sortie F31 Interface IO Link Plage de pression en bar Exécution 1 céramique absolue En bar 0001 02 5 En psi 0015 0050 Exécution 3 céramique absolue En bar 0001 1 1 bar 01 0 02 5 06 0 0010 0016 En psi 0015 0030 0050 0150 0250 0500 0089 14 75 psi Indice de modification 000 Sta...

Page 80: ...ment mécanique 4 G1 4 A ISO 1179 2 DIN 3852 extérieur avec plage de pression en bar 7 9 16 18 UNF 2A SAE6 extérieur avec plage de pression en psi 9 Orifice taraudé DIN 3852 G1 4 avec plage de pression en bar Raccordement électrique 6 Embase M12X1 4 pôles livré sans connecteur Sortie F31 Interface IO Link Plage de pression En bar 0040 0100 0250 0400 0600 En psi 1000 3000 6000 9000 Indice de modific...

Page 81: ... 06 02 4 pôles Connecteur coudé avec 2m de câble Code art 6006790 ZBE 06 05 4 pôles Connecteur coudé avec 5m de câble Code art 6006789 Couleur Pin 1 brun Pin 2 blanc Pin 3 bleu Pin 4 noir 20 2 POUR LE RACCORDEMENT MECANIQUE ZBM 3000 Collier pour fixation murale à visser Matériau partie inférieure TPE Santoprene 10187 Matériau partie supérieure acier DIN 95381 1 4571 Code art 3184630 ...

Page 82: ...xation murale à souder Matériau collier à souder QSTE340TM galvanisé EN 12329 FE ZN8 B Matériau partie inférieure TPE Santoprene 10187 Matériau partie supérieure acier DIN 95381 1 4571 Code art 3184632 ZBM 3200 Protection contre les projections d eau Matériau Elastollane S60 A15 SPF 000 Code art 3201919 ...

Page 83: ...IO Link 27 Edition 04 02 2016 HYDAC ELECTRONIC GMBH Code art 669897 F 21 Encombrements Embase M12x1 4 pôles Diamètre orientation corps 340 Joint elastomère DIN 3869 orientation corps 270 Joint torique 11 89x1 98 ...

Page 84: ...ce se tient à votre disposition HYDAC SERVICE GMBH Hauptstr 27 D 66128 Saarbrücken Allemagne Tél 49 0 6897 509 1936 Fax 49 0 6897 509 1933 Remarque Les indications de cette notice se réfèrent aux conditions de fonctionnement et cas d utilisation décrits Pour des conditions d utilisation et de fonctionnement différentes veuillez vous adresser au service technique compétent Pour toute question techn...