Self-contained emergency lighting luminaire
5/8
IMM - KWADRA FL LED - AT_CT - PL_EN V01
IP65/IP20
EN
KWADRA FL LED
INSTALLATION AND MAINTENANCE MANUAL
MOUNTING TYPE
Mounting in a suspended ceiling
OPERATING MODE
NM
– NON-MAINTAINED –
luminaire operates in emergency
mode after power supply failure
SM
–
SWITCHED MAINTAINED
– luminaire operates in emer
-
gency mode after power supply failure, mains operation
controlled by the switched phase L’
N
–
NIGHT – luminaire operates in emergency mode after po
-
wer supply failure, mains operation controlled from the
CT central unit
SYSTEM VARIANT
AT
– AUTOTEST –
internal components, battery and light
source tests being performed automatically
CT
–
CENTRALTEST –
internal components, battery and light
source tests being performed on command from the
main unit of central management system
TESTS
The microcontroller-based control and test unit performs automatically (AT) or on order from the central management system (CT) two types of tests:
TEST A
–
internal components and light source test lasting 60 seconds – performed every 30 days for the AT system variant
TEST B
–
internal components, light source and operation duration test (till the battery is fully discharged) – performed every 360 days for the AT system variant
The first TEST A will be performed 10-30 days after the power-up, and TEST B 30-90 days, after the power-up (AC, battery).
OPTICS
AREA
–
(AR) symmetrical light distribution in all directions, rec
-
ommended for use in places of considerable height
or to illuminate fire points
AREA / AREA PLUS
ROAD
ROAD PLUS
SIDE
ROAD
–
(RO) light distribution mainly along the escape route, rec
-
ommended for use in high corridors
ROAD
PLUS
–
(RP) light distribution mainly along the escape route
with a much greater range than for the ROAD optics, for
small heights
SIDE
–
(SD) light distribution directed to one side, for wall
mounting, spot illuminating
TECHNICAL DATA
Supply voltage
230V AC 50/
60HZ
Current consumption (3W)
NM
4,5W
SM, N
10W
Protection class
I
Ingress protection
IP65/IP20
1)
Light source type
LED module
2)
Light source temperature
5700K
Light source supply power
1W, 2W, 3W
Light source lifespan
> 50 000h
Battery type / voltage
Ni-MH
4,8V
Battery capacity
1,6; 2,1; 4,0Ah
Battery recharging time
< 24h
Emergency operation time (taw)
1h, 2h, 3h
Ambient temperature range
+5 – +35˚C
TE:
3)
-25 – +40˚C
Supply cable cross-section area
NM
3 x 0,5-2,5mm
2
SM, N
4 x 0,5-2,5mm
2
Supply cable diameter
≤ 13mm
Communication cable diameter
CT
≤ 7mm
Suitable for through wiring
YES
Suitable for surface wiring
NO
1)
Luminaire in internal/external zone, IP20 for luminaires without seal;
2)
Non-exchangeable but serviceable light source;
3)
TE – extended temperature range