Installation and Maintenance Manual
20
Connecting a Master / Slave Pair
Configuring two operators to be a Master & Slave pair is easy with the Smart Touch Controller. There is
no need to order a special model or any adapters. The area of the board marked Dual Gate employs a
3-wire RS485 serial port for communication between Master & Slave operators.
1. An electrical conduit for the interconnecting wires must span between the two operators.
2. Complete the installation of both of the operators as separate machines and verify that their basic
functions are correct as solo operators before interconnecting them.
3. The two gate operators should be supplied by home runs from separate 20 Ampere circuit
breakers in the main panel, but if there is only one circuit, be absolutely certain that the breaker
and wire size is sufficient for the load of two motors. See the Appendix.
4. External control inputs, vehicle detectors and entrapment protection sensors may be connected
to either gate operator without regard to preference.
5. To interconnect the two operators, route a shielded twisted pair with an internal ground wire
between the electric control boxes and connect to the RS485 Dual Gate terminals, in matching
order on both machines: In the RS485 shaded area connect the terminals for Master Com to
Slave Com with the ground shield trace wire, and connect the Master A to Slave A and the
Master B to Slave B using the insulated twisted pair of wires.
6. The Installer Menu in each machine must be set as a Master or a Slave under menu item [dg__].
Set one operator as a Slave [dg_1] and the other as a Master [dg_2]. If the function of any
external input is to be different than the factory default, configure for the desired function on the
operator where that input is connected. Internal functions, such as the close timer or reversal
distance, are controlled by the Master operator regardless of the settings in the Slave.
7. Once set as a Master or a Slave the operators will be in constant communication with each other.
If that communication stops because the wires become severed or one operator is turned off,
both machines will cease functioning and the LCD will display Err4, which is a Master/Slave
communication error. This error cannot be reset until both machines are functional and
communicating properly again.
Summary of Contents for HTG 320-2
Page 16: ...Installation and Maintenance Manual 10 Components of the Barrier Arm Gate Operator ...
Page 19: ...Installation and Maintenance Manual 13 ...
Page 20: ...Installation and Maintenance Manual 14 ...
Page 21: ...Installation and Maintenance Manual 15 ...
Page 25: ...Installation and Maintenance Manual 19 ...
Page 41: ...Installation and Maintenance Manual 35 E95 ...
Page 54: ...Installation and Maintenance Manual 48 ...
Page 55: ...Installation and Maintenance Manual 49 ...
Page 57: ...Installation and Maintenance Manual 51 ...
Page 58: ...Installation and Maintenance Manual 52 Parts Breakout ...
Page 59: ...Installation and Maintenance Manual 53 Parts Breakout ...
Page 60: ...Installation and Maintenance Manual 54 Parts Breakout ...
Page 61: ...Installation and Maintenance Manual 55 Parts Breakout ...
Page 62: ...Installation and Maintenance Manual 56 Parts Breakout ...
Page 63: ...Installation and Maintenance Manual 57 Parts Breakout ...
Page 64: ...Installation and Maintenance Manual 58 Parts Breakout DC Power Supply Battery Pack Components ...