To open the damper, insert the screwdriver into the 

shaft (parallel to the ventilation duct axis) and turn 

counterclockwise

To close the damper, press the thermal fuse head with 

a screwdriver

Options:

• For this self-operating version, the double contact – S and the 4-contacts – S2 - are available as an option 

  (factory option or after-sales kit):

The 4-contact – S2 - consists of:

• 

electric limit switch indicating CLOSED position

• 

electric limit switch indicating OPEN position

• 

additional electric limit switch indicating CLOSED position

• 

additional electric limit switch indicating OPEN

FD25/FD40 solenoid actuator version

Activation:

• Manual activation: Push the release button.

• Self-operating activation: With a fuse at 72 ºC 

• Remote activation: By emission or break of current (solenoid with 24/48 V automatic voltage)

Resetting:

- Manual resetting: Tour the lever counter-clockwise

Reminder:

• For this version with remote activation, the double contact S (OPEN / CLOSED) are mounted as standard equipment

• The 4-contact – S2 - are available as an option (factory option or after-sales kit).

7. ELECTRICAL CONNECTIONS

FD25 MANUAL FUSE ONLY MECHANISM

• Electrical wiring of the S option

 

Electronic control board

FC = Limit switch - end  

C = common 

 

 

NF = normally closed

DC = Limit switch - start 

NO = normally open

MANUAL FUSE ONLY MECHANISM UPGRADABLE TO SOLENOID ACTUATOR

• Electrical wiring of solenoid option

 

Main electronic control board of coil supply

MOT = not in use 

 

MAG = solenoid power supply terminals (24 or 48 VDC)

• Electrical wiring of the S option

 

Main electronic control board of coil supply

FC = Limit switch - end  

C = common 

 

 

NF = normally closed

DC = Limit switch - start 

NO = normally open

Summary of Contents for Klimaoprema FDC25

Page 1: ...a hr TECHNICAL MANUAL FDC25 FDC40 Circular Fire damper SUMMARY 1 PRODUCT PRESENTATION 2 2 DIMENSIONAL RANGE 2 3 DIMENSIONS 3 4 STORAGE AND HANDLING 4 5 INSTALLATION AND IMPLEMENTATION 4 6 CONTROL MECH...

Page 2: ...ng to standard EN 1751 class C Approved for installation in a concrete wall a concrete slab plasterboard wall and gypsum blocks wall Operating mechanism completely outside the wall Easy to install Mai...

Page 3: ...PLEMENTATION 5 1 INSTALLATION Mounting is possible with the blade axis in horizontal or in vertical position The installation must comply with the tests that were performed during certification s expl...

Page 4: ...nd the wall with mortar Cover the mortar with GFK gypsum boards 12 5 mm thick Place the damper in an opening of 70 mm or more The Kit is universal for all dimen sions and must be cut to fit the specif...

Page 5: ...onstruction Place the damper in an opening of 70 mm or more Fix the damper to the wall using screws Fill the space between the damper and the wall with mortar Cover the mortar with GFK gypsum boards 1...

Page 6: ...ion with L profiles 30x30x3mm Additionally fix profiles to duct with self tapping screws and screw them to wall with 4 5x50 screws On connection wool wall apply glue Isover BSK in thickness of 2mm Add...

Page 7: ...chott Installation material Fire damper FDC Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Recommended wall opening for fire damper installation is 400mm but openings from 80 6...

Page 8: ...e activation By emission or break of current solenoid with 24 48 V automatic voltage Resetting Manual resetting Tour the lever counter clockwise Reminder For this version with remote activation the do...

Page 9: ...device is released the damper will open Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric actua tor clockwise Damper can be l...

Page 10: ...nside or outside duct If checking is needed for proper functioning of fire damper pushing the switch on the thermal tripping device will close damper When switch on tripping de vice is released the da...

Page 11: ...0kg m3 100mm EI 120 ho i o S 500Pa Nominal activation conditions sensitivity according to ISO 10294 4 Passed sensing element load bearing capacity sensing element response temperature Response delay c...

Page 12: ...23 22 NOTES...

Page 13: ...Klimaoprema d d Gradna 78A 10430 Samobor Croatia Tel 385 0 1 33 62 513 Fax 385 0 1 33 62 905 info klimaoprema hr www klimaoprema hr...

Reviews: