Table 5 Overcurrent protection characteristics of circuit breakers for
motors
Rated current In
(A)
Thermal release (ambient tempe40°C)
Operating current
of
electromagnetic
release (A) [Note]
1.0 In non-
operating time
(h)
(initial state: cold
state)
1.2 In operating
time (h)
(initial state:
thermal state)
1.5 In operating
time (min)
(initial state:
thermal state)
7.2 In operating
time (s)
(initial state: cold
state)
In≤63
>2
≤2
≤2
2<Tp≤10
(12±2.4)In
63<In≤250
≤
4
4<Tp≤10
250<In≤800
≤8
6<Tp≤20
[Note]: The operating current of the electromagnetic release of H8M-
630 and 800 (400 A ≤ In ≤
800 A) is (5±1) In to 14 In.
Adjustable reference value: Low (4 ~ 6) In; Relatively low (6 ~ 8.3) In; Relatively high (8.3 ~ 10.9)
In; High (10.9 ~ 14) In.
6 Circuit Breaker Accessories
6.1 List of accessory models (see Table 6).
Table 6 List of accessory models
Shell frame level rated current Inm
(A)
63
100
250
400
630, 800
Int
er
nal
ac
ces
sor
ies
Alarm contact
B1
B2
B3
B4
Auxiliary contact
F1
F2
F3
F4
Shunt trip
FL1
FL2
FL3
FL4
Undervoltage release
QY1
QY2
QY3
QY4
Accessory terminal
JX
Special release with prepaid
kilowatt-hour meter
Y
Ex
ter
nal
ac
ces
sor
ies
Rotation operating handle
CS1-63
CS1-100
CS1-250
CS1-400
CS1-630
Electric operating mechanism
MDX0
MDX1
MDX2
MDX3
MDX4
Mechanical
interlock
3-pole
N1-3
N2-3
N3-3
N4-3
N5-3
4-pole
——
N2-4
N3-4
N4-4
N5-4
6.2 Rated values of auxiliary contacts and alarm contacts
Conventional thermal current Ith = 6 A;
Rated working current Ie = 0.79 A (230 V, AC) Ie = 0.47 A (400 V, AC);
Ie = 0.15 A (220 V, DC).
6.3 Shunt trip parameters
Rated voltage Us: AC: 110 V, 230 V, 400 V; input capacity: 180 VA;
DC: 24 V, 48 V, 110 V; input capacity: 60 W.
The circuit breaker can interrupt reliably under (70% ~ 110%) Us, and