background image

- 1 - 

The H8M Series Molded  Case  Circuit Breaker (hereinafter referred to as 

“circuit breaker”) is the high-tech product in the 21st century. This product is 

characterized by advanced design, reliable performance, high technical 

indicators, beautiful appearance, and small size. 

1  Purpose and Scope of Application 

This circuit breaker is suitable for the power system with AC 50 Hz, rated 

isolation voltage up to 800 V, rated working voltage up to 690 V and rated 

current up to 800 A. It is used to distribute electric energy and protect 

circuits and power supply equipment from overload, short circuit, 

undervoltage and other faults, and to prevent the infrequent operation of 

the motor. 

2  Standards Followed 

The product complies with GB/T 14048.2-2008 

Low-voltage Switchgear and 

Controlgear  —  Part 2:

 

Circuit-breakers

  and IEC 60947-2 

Low-voltage 

Switchgear and Controlgear — Part 2: 

 

Low-voltage Circuit Breakers

, etc. 

3  Model Description 

 

 

Overload alarm without tripping is denoted by “I” 
Flashover distance: No code with flashover; Code W without flashover 
Wiring method:   No code with wiring in front of the plate; Code H with 

wiring behind the plate, C for plug-in connection, and 

CH for pull-out connection (only for 3 poles) 

No code for conventional products, and code Y with the special release 

with prepaid kilowatt-hour meter 
Application code: No code for power distribution; Code 2 for motor protection 
Internal accessory code (see Table 2) 
Overcurrent release type (see Table 1) 
Type of neutral pole (N pole) of 4-pole circuit breaker (note) 
Number of poles of circuit breaker: 3 for 3 poles; 4 for 4 poles 
Circuit breaker rated current In (A) (see Table 3) 
Operation mode:  No code for handle direct operation; 
 

Code M for electrical operation; 

 

Code Z for handle rotation operation  

Short-circuit breaking capacity level: C — Basic type; S — Standard type; 
H — Advanced type; U — Current limiting type 
Shell frame level rated current Inm (A) (see Table 3) 
Molded Case Circuit Breaker 
Design number 
Enterprise code 

 

Note: In 4-pole products, two types are provided for the neutral pole (N pole): 

Type A: The N pole is not equipped with an overcurrent release and is normally on, and 

is not opened/closed with the other three poles. 

Type B: The N pole is not equipped with an overcurrent release, and is closed/opened 

with the other three poles. 

 

 

Summary of Contents for 100H H8M-100U

Page 1: ...peration Instruction Product Certificate This product has passed the inspections and meets the requirements of GB T 14048 2 and therefore is allowed to leave the factory Inspector Date of inspection S...

Page 2: ...method No code with wiring in front of the plate Code H with wiring behind the plate C for plug in connection and CH for pull out connection only for 3 poles No code for conventional products and cod...

Page 3: ...reaker is suitable for the following working conditions 4 1 The ambient air temperature shall not be higher than 40 C or lower than 5 C 4 2 Altitude 2 000 m 4 3 The relative air humidity shall not exc...

Page 4: ...3 4 3 4 3 3 Rated insulation voltage Ui V AC 600 AC 800 AC 800 Rated impulse withstand voltage Uimp kV 8 Flashover distance mm 50 0 50 0 50 0 Rated ultimate service short circuit breaking capacity Ic...

Page 5: ...50 75 75 100 100 125 125 50 50 75 75 100 100 125 125 Operation performance times Energizing 7 500 7 500 7 500 De energizing 10 000 10 000 10 000 Outline dimensions mm a 140185140180 140 140 2102802102...

Page 6: ...odels see Table 6 Table 6 List of accessory models Shell frame level rated current Inm A 63 100 250 400 630 800 Internal accessories Alarm contact B1 B2 B3 B4 Auxiliary contact F1 F2 F3 F4 Shunt trip...

Page 7: ...of the input terminal of the power supply is AC 50 Hz 230 V 400 V Figure 1 Shunt trip control circuit design 6 4 Parameters of the undervoltage release Rated voltage Ue AC 110 V 230 V 400 V DC 24 V 4...

Page 8: ...MDX1 MDX2 MDX3 MDX4 Rated working voltage Ue V AC 110 V 230 V 50 Hz DC 110V 220 V Starting current A 0 5 2 Operating time S 0 8 Rated operating frequency times h 180 120 Mechanical life times 15 000 9...

Page 9: ...shall be tightened Table 8 Cross section area of the connecting conductor Rated current In A 10 16 20 32 40 50 63 80 100 125 150 160 175 200 225 250 300 350 400 Cross section area of the conductor mm...

Page 10: ...tances the fees for repair still shall be charged even within the warranty period 1 Misuse self modification improper maintenance etc 2 Use beyond the standard specification requirements 3 Falling dam...

Page 11: ...Group Zhejiang High tech Co Ltd Address Wenzhou Bridge Industrial Zone Yueqing City Zhejiang Province Tel 0577 62889999 Fax 0577 62885588 Postal code 325603 http www huyu coin cn Service Hotline 400 8...

Reviews: