Nozzle keeps shutting off or won't dispense...
1. Make sure dispenser is on and activated.
2. Slow down flow rate - use lower notch
on clip.
3. Clean spout tip end.
4. Clean or replace filter.
5. Inspect Safe-T-Break
®
.
6. Replace spout assembly.
7. Check dispenser pressure - 19 psi /
1.3 bar to activate nozzle.
8. Remove nozzle & drain hose.
Nozzle won't shut off...
1. Check flow rate - minimum of 3 gpm /
11.3 Lpm required.
2. Remove nozzle and drain hose.
Nozzle leaks...
1. Check for loose spout.
2. Check hose connection.
3. Check for cracks in nozzle and hose threads.
Low flow rate...
1. Remove Flo-Equalizer
®
(if equipped).
2. Verify dispenser is not in slow flow rate mode.
3. Check for system leak.
Flow rate above 10 gpm / 37.9 Lpm...
1. Verify Flo-Equalizer
®
being used - either inside
or outside dispenser.
2. Check Flo-Equalizer
®
for debris.
Fuel Type
Test and warranty for gasoline and diesel fuel
Flow Rate
Unleaded w/o Flo-Equalizer
®
= 14 gpm / 52.9 Lpm
Light Duty Diesel w/o Flo-Equalizer
®
= 16 gpm / 60.6 Lpm
Body
Die cast aluminum
Disc
Fluorocarbon
Packing
Double O-ring seal protected by fiber reinforced Teflon
®
Lever
One piece contoured steel
Shipping
Unleaded = 3.1 lbs / 1.4 kg
Weight
Light Duty Diesel = 3.1 lbs / 1.4 kg
Threads
¾" / 19.1 mm NPT
Spout
Unleaded = 13/16 in / 20.6 mm O.D. Light Duty Diesel = 15/16 in / 23.8 mm O.D.
Case Quantity
15
Listings
Default
^ NOT LISTED
TROUBLESHOOTING GUIDE
GENERAL TECHNICAL DATA
Husky Corporation • 2325 Husky Way • Pacific, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 3 009216-15 10/2019
1. Activate dispenser.
2. Insert spout into fill pipe opening.
3. Lower hose end of nozzle so the spout spring catches
the inside of the fill pipe.
4. Raise the lever and begin fueling.
5. Nozzle will shut off automatically when the tank is full.
6. Wait 15 seconds to allow any fuel remaining in the
spout to drain.
7. Remove nozzle from fill pipe by raising hose end of
the nozzle.
8. Return nozzle to nozzle boot.
NOTE: Nozzle is equipped with a unique Flo-Stop
®
device that shuts off the
nozzle if it falls from fill pipe or raises above horizontal.
1. Verify nozzle has hold open clip.
2. Verify dispenser is turned off.
3. Place nozzle spout into test can.
4. Pull up lever and latch clip - a small amount of fuel
may flow until the line pressure is relieved.
5. Turn on dispenser and select grade - nozzle should
not dispense fuel.
6. Release the lever.
7. Pull up lever and latch clip - nozzle should dispense
fuel.
8. Turn off dispenser - nozzle should stop dispensing
fuel.
9. Turn dispenser on and select grade - nozzle should
not dispense fuel.
NOTE: The no pressure / no flow device fulfills the NFPA Code 30A
requirement regarding self-service nozzles with a hold open latch. If nozzle
fails item #5 or #9, verify dispenser is not allowing constant pressure to the
hose. If dispenser tests OK, replace nozzle.
OPERATION INSTRUCTIONS
PRESSURE ACTIVATION TEST INSTRUCTIONS