background image

1.  Turn off the dispenser and relieve line pressure.

2. Apply approved sealant thinly to male threads of hose. Do not use Teflon

®

 tape.

3. Tighten approximately 1 to 2 turns past hand tight - do not overtighten.

4.  Test nozzle for proper automatic shut off between 5 - 10 gpm / 18.9 -

 

37.9 Lpm.

5. Perform pressure activation test (no pressure / no flow test).

6. Pressurize system and visually inspect for leaks.

USE WRENCH ON HOSE NUT ONLY.

TESTING / MAINTENANCE / INSPECTION

XS

®

 

w/

Mate 

Guards

WARNING 

Designed for use at motor fuel dispensing facilities only.

Husky Corporation • 2325 Husky Way • Pacific, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com 

Page 1                                                                      009216-15 10/2019

INSTALLATION INSTRUCTIONS

IF DRIVE OFF OCCURS

Daily

• Check for leaks / stains.

• Check for loose spouts.

• Check for damage.

• Check for bent lever.

•  Check for broken clip / trigger 

spring.

Monthly

• Check nozzle auto shut off.

•  Check no pressure / no flow.

• Check "remove after" date.

Annually

•  Check for electrical 

conductivity.

• Lubricate main valve stem.

•  All drive aways, maintenance and 

inspection activities must be logged 

using the serial number of the 

individual product.

•  Apply city, state, or federal testing 

 

regulations as appropriate.

ANY TEST / INSPECTION FAILURE 

REQUIRES IMMEDIATE EQUIPMENT 

REPLACEMENT OR REMOVAL FROM 

SERVICE.

MADE IN THE USA

Pressure Activated Conventional Nozzles

Recommended Installation, Maintenance

and Inspection Instructions

•  Turn off the dispenser and relieve line pressure.

• Visually check for fractured spout shear groove.

• Check for leaks.

•  Check spout tip - should be in round and sensing port should be clear of debris.

•  Test nozzle for proper automatic shut off between 5 - 10 gpm / 18.9 - 37.9 Lpm.

• Check for electrical conductivity.

• Perform pressure activation test (no pressure / no flow test).

Important safety instructions - save these instructions in a readily accessible location

See Listings for details

E159503

E159504

^E159504N

E159507

^E1302704N

E1595133

^E1595133N

E12193133

E1219359

WARNING: 

Cancer and Reproductive Harm - www.P65Warnings.ca.gov

Summary of Contents for XS E159503

Page 1: ... Check remove after date Annually Check for electrical conductivity Lubricate main valve stem All drive aways maintenance and inspection activities must be logged using the serial number of the individual product Apply city state or federal testing regulations as appropriate ANY TEST INSPECTION FAILURE REQUIRES IMMEDIATE EQUIPMENT REPLACEMENT OR REMOVAL FROM SERVICE MADE IN THE USA Pressure Activa...

Page 2: ...expressly excluded Husky reserves the right to change or improve the design of any Husky fuel dispensing equipment without assuming any obligations to modify any fuel dispensing equipment previously manufactured Use of equipment is at individuals own risk Always abide and adhere to city state and federal regulations regarding use and installation of dispensing equipment Always follow the product m...

Page 3: ... TROUBLESHOOTING GUIDE GENERAL TECHNICAL DATA Husky Corporation 2325 Husky Way Pacific MO 63069 Phone 800 325 3558 Fax 636 825 7300 www husky com Page 3 009216 15 10 2019 1 Activate dispenser 2 Insert spout into fill pipe opening 3 Lower hose end of nozzle so the spout spring catches the inside of the fill pipe 4 Raise the lever and begin fueling 5 Nozzle will shut off automatically when the tank ...

Page 4: ... cover 2 Snap new handle cover into place WAFFLE SPLASH GUARD Model 001808 1 Remove old waffle splash guard 2 Install new waffle splash guard over spout lock nut POPD CLEAR COVER Model 006628 1 Trim advertisement to 3 75 in 95 25 mm x 3 75 in 95 25 mm 2 Notch corners of advertisement approximately 375 in 9 5 mm x 375 in 9 5 mm 3 Turn clear cover inside out 4 Center advertisement on POPD guard usin...

Reviews: