INSTALLATION 

 
THIS APPLIANCE MUST BE INSTALLED BY AN AUTHORISED PERSON.  Refer to heater 
data plate for specifications of gas type, gas consumption, burner pressure and water pressure. 
 
This appliance must be installed in accordance with local regulations and A.G.A. Installation Code 
AG 601. 
 

FLOW RATES 

The Hurlcon Pool Heater requires a minimum of 150 litres per minute flow and the maximum 
permissible flow rate is 450 litres per minute.  For flow rates in excess of 450 litres per minute, an 
external by-pass valve must be fitted. 
 

WATER CONNECTIONS 

The heater should always be installed after the pump and filter.  The water connections are located 
on the right hand side of the heater.  Left hand connection models are available by special order.  
The inlet and outlet are clearly marked.  Water connections require 40 mm PVC glue in plumbing. 
 
All automatic sanitising devices must be installed after the heater and in such a way that the 
sanitiser cannot enter the heater without first mixing with the water in the pool or spa.  Sanitisers 
that are connected prior to the heater will void heater warranty. 
 
The Hurlcon Pool Heater incorporates a balanced flue terminal and is suitable for outdoor 
installation. 
 

PLUMBING DIAGRAM

 

 

 

To Solar 

From Solar 

From Pool 

Pump 

Filter 

Heater 

Chlorinator 

Return to Pool 

Heater Diagram 
1. 

Plumbing in high pressure 40mm or 50mm PVC pipe 

2. Connection 

to 

heater 

in Class 12 or higher 

3. 

All automatic Chlorinators or Sanitisers Must be installed after heater 

PVC Piping 

Summary of Contents for HX 120

Page 1: ...site www hurlcon com au Email service hurlcon com au Information and specifications subject to change without notice Victoria Ph 03 9765 9765 Fax 03 9764 9009 New South Wales Ph 02 9674 8544 Fax 02 96...

Page 2: ...nce Instructions 8 Energy saving Tips 8 Winter Operation 8 Installation Installation Instructions 9 Flow Rates 9 Water Connections 9 Plumbing Diagram 9 Heater Dimensions 10 Indoor Installation 10 Vent...

Page 3: ...nstructions local gas fitting regulations the AGA Installation Code AG 601 and any other relevant statutory authorities Refer to data plate for details of gas type gas consumption and burner pressure...

Page 4: ...ct pool or spa mode 7 Set thermostat to desired setting and the ON OFF switch to turn the heater ON 8 The heater will ignite in around 10 seconds 9 If the appliance will not operate follow instruction...

Page 5: ...cium hardness and temperature These measurements must be at the correct levels to maintain balanced water and effective sanitation of your pool Balanced water will help prevent corrosion of your heate...

Page 6: ...or two minutes after the set point has been reached If the time delay is activated the symbol L will be displayed This is part of normal operation The thermostat can be set to temperatures between 10...

Page 7: ...r greater than 0 C phone for at 0 C freeze conditions service F1 Thermostat reads greater Allow water to cool than 45 C turn heater off then on again F2 Mechanical Hi Limit greater Allow water to cool...

Page 8: ...8 C or lower This is accepted as a comfortable and healthy swimming temperature 3 Use an accurate thermometer 4 Set timeclock to start filtration and circulation system no earlier than daybreak The po...

Page 9: ...s are located on the right hand side of the heater Left hand connection models are available by special order The inlet and outlet are clearly marked Water connections require 40 mm PVC glue in plumbi...

Page 10: ...talling the heater indoors it is imperative that an adequate supply of fresh air is provided for combustion Failure to provide adequate ventilation voids all warranties and may be a danger to persons...

Page 11: ...l spa blowers in the same room as a gas heater This is potentially dangerous to spa users Do not store chemicals or fuel in the same room as the gas heater This may cause fire or explosion When instal...

Page 12: ...built in pressure regulator and pressure test point On starting the heater a manometer must be used and burner pressure checked against the heater data plate The gas valve regulator may need to be adj...

Page 13: ...isplay to indicate water flow 4 Set thermostat to ON and press the button repeatedly until set temperature is greater than water temperature Thermostat should now display 5 After a few seconds the bur...

Page 14: ...he nominal burner pressure listed below 7 To adjust gas valve regulator remove regulator adjustment cap and using a screwdriver turn plastic bush clockwise to increase anti clockwise to decrease burne...

Page 15: ...rner assembly and withdraw 8 Remove the four Phillips head screws securing the injector manifold to the burner tray 9 Remove burner injectors and replace with desired gas type injectors 10 Remove regu...

Page 16: ...played Refer to fault indication table HEATER SHORT CYCLING RAPID ON AND OFF OPERATION Possible cause Remedy Insufficient water flow Clean filter and pump strainer Defective wiring Repair or replace w...

Page 17: ...re Switch N O Hi Limit N C 45 Hi Limit N C 70 A N E Transformer Genus IV Thermostat Sensor 4 Pin Plug Ignitor Flame sensor Violet Brown Earth Post 6 Pin Plug Ignition Module Brown Green Yellow Orange...

Page 18: ...n and operating instructions The warranty shall not apply to any heaters or parts which have been subject to accident negligence alteration abuse or misuse Corrosion of the heat exchanger is caused by...

Reviews: