HX Pool and Spa Heater
Page 11
The following diagram is provided as a guide only. All flueing and installation work must be
carried out by an authorized person. Flueing must conform to local regulations and to A.G.A.
installation code AG 601. Care must be taken to provide the correct ventilation and correct
flueing materials in close proximity to combustible surfaces.
An indoor draught diverter must be purchased from Hurlcon and fitted to unit in
accordance with Hurlcon’s Instructions and Installation Codes before the heater can be
enclosed.
Do not install spa blowers in the same room as a gas heater. This is potentially dangerous to
spa users.
Do not store chemicals or fuel in the same room as the gas heater. This may cause fire or
explosion. When installing in a garage the HX Heater must be installed 450 mm above floor
level.
CLEARANCES
The heater must be installed at least 500 mm from any combustible surface. Clearances must
comply with AG 601.
Clearances from non combustible surfaces are:
Front 500mm
Both sides
150mm
Rear 150mm
Above 500mm
Combustible Surfaces
500mm Minimum
Heater must be installed on a fireproof base.
1500
60
0
Upper grille for fresh
air ventilation
Lower grille for fresh
air ventilation
●
Approved gas
termination cowl
Bolted
sleeve to
connect flue
Draft diverter
purchased
from Hurlcon