• Humidification, Dehumidification function:

Dehumidification Mode:

 When the measured Humidity is higher than or equal to the set value 

+ hysteresis, the relay picks up to start the output; When the measured Humidity below the set 

value, the relay off and close the  

output.

 

Humidification mode: 

When the measured Humidity is higher than or equal to the set value, 

the relay off, turn off the output; When the measured Humidity below the set value - hysteresis, 

the relay picks up to start the output.

 

Example for Setting: If it is set to Humidification mode, set the Humidity to 75%, hysteresis is set to 5, 

then when the measured Humidity is higher than or equal to 75%, the relay is off, close the output. 

When the temperature is below 70%, pick up the relay again, to start the output.

 

Example for Setting: If it is set to Dehumidification mode, set the Humidity to 75%, hysteresis is set to 

5, then when the measured Humidity is below 75%, the relay is off, close the output. When the Humidi-

ty is higher than or equal to 80%, pick up the relay again, to start the output.

 

• Humidification, Dehumidification mode setting:

Press “SET” key and hold more than 3 seconds to enter the menu display, the screen appears 

“HC” code, press the “SET” key to display the working mode, press the “

 

or

 

” to adjust the 

display, C means Dehumidification mode; H means Humidification mode.

 

• Hysteresis function:

Hysteresis setting limits the maximum interval between the opening and stopping, this machine 

minimum interval between the opening and stopping is 1 %, the maximum is 15 %.

 

• Hysteresis settings:

Press “SET” key and hold more than 3 seconds to enter the menu display, with “

 

or

 

” key 

adjusted to the screen, appearing “D” code, press the “SET” key to display the hysteresis set va-

lue, press “

 

or

 

” key to adjust the parameters.

 

• Humidity calibration function:

When there is deviation between the measuring Humidity and standard Humidity, use the Hu-

midity calibration function, make the machine measurements value consistent with the stan-

dard Humidity, the after calibration Humidity = the before calibration Hu calibration va-

lue (calibration value can be positive number, negative number, and 0).

 

• Humidity calibration settings:

Press “SET” key and hold more than 3 seconds to enter the menu display, with “

 

or

 

” key 

adjusted to the screen, appearing “CA” code, press the “SET” key to display the temperature cali-

bration settings, press “

 

or

 

” key to adjust the parameters.

 

For example: When we measure the probe Humidity was 75 %,it displays 75% as the CA is 0, it displays 

76% as the CA is 1, it displays 74 % as the CA is -1. This function is generally applied when the probe 

can not measure directly the measured object.

 

• Delay Protection Setting:

Press “SET” key and hold more than 3 seconds to enter the menu display, with “

 

or

 

” key 

adjusted to the screen, appearing “PT” code, press the “SET” key to display the delay setting va-

lue, then press the “

 

or

 

” key to adjust the parameters.

 

• Upper and lower limit functions:

The setting of HS and LS limit the set range of control Humidity point, for example: HS is set to 

75, LS is set to 50, the control Humidity can only be adjusted between 50 and 75, when the con-

trol Humidity to 50 then press “

” key, the display will remain on the status of 50 and not de-

crease; when the control temperature to 75 then press “

” key, the display will on the status of 

75 and not increase. If the set point outside this range, it needs to firstly change the value of HS 

and LS, then it can be achieved.

 

• Upper and lower limit settings:

Press “SET” key and hold more than 3 seconds to enter the menu display, with “

 

or

 

” key 

adjusted to the screen, appearing “HS” or “LS” code, press the “SET” key to display the upper or 

lower limit set value, then press “

 

or

 

” key to adjust the parameters. HS means upper limit. 

LS means lower limit.

14

Summary of Contents for HR6

Page 1: ...instrucciones de uso y puesta en marcha de su nuevo humidor y humidificador electr nico Hr6 Manual and instructions for use and implementation of your new humidor and electronic humidifier Hr6 Manual...

Page 2: ...bla Esta oscilaci n produce iones negativos que ayudan a refrescar el aire El ventilador instalado en el equipo se encarga de repartir la humedad por el humidor El humidificador paraliza autom ticamen...

Page 3: ...e ning n ajuste del regulador poe que ya est configurado Si lo hace puede alterar su funcionamiento 3 Al inicio y hasta que el espacio a humedecer no se sature se consumir bastante agua Esto es normal...

Page 4: ...onectarse de la red el ctrica Saque el humidificador del mueble y vac e el agua del dep sito teniendo mucho cuidado de que el agua no moje la parte electr nica del equipo Limpie el dep sito y la cer m...

Page 5: ...lizador no est da ado y no gira el ventilador puede ser que haya cambiado la polaridad de la toma redonda que va al humidificador o que haya habido una sobretensi n que haya da ado el ventilador El hu...

Page 6: ...ndo est apagado para encender Encendido pulse la tecla RST tres segundos y sostenga para apagar SET A Presione una vez la tecla SET para entrar en el control de la temperatura y presione las teclas o...

Page 7: ...diferencia que hay entre el valor que da el regulador con el que da el higr metro externo el valor de esta calibra ci n puede ser 0 un n mero positivo o un n mero negativo Configuraci n de la humedad...

Page 8: ...dificador debe estar bien conectado con el terminal si no la fiabilidad de la m quina se reduce Cuando se conecten los cables por favor separe fuente de alimentaci n rel s y sensores o de lo contrario...

Page 9: ...ammed humidity and starts again when it has fallen about 5 The humidifier has a tank to store water it must be distilled to prevent impurities from running water and to extend the life cycle of the hu...

Page 10: ...gs that have already been configured Otherwise a malfunction may occur 3 At the beginning and until the area is fully humidified a lot of water will be consumed which is normal at this stage After the...

Page 11: ...uipment should be disconnected from the main power supply Remove the humidifier of the cabinet and empty the water from the tank taking care to avoid wetting the electronic parts of the humidifier Cle...

Page 12: ...is not damaged and the fan does not turn it may be that you have changed the polarity of the round socket that goes to the humidifier or that an electricity surge has been damaged the fan The humidifi...

Page 13: ...ng mode B Press and hold SET key for three seconds to enter the system menu settings press the or key to select the adjustment menu press SET key once to enter the appropriate para meter settings pres...

Page 14: ...calibration function When there is deviation between the measuring Humidity and standard Humidity use the Hu midity calibration function make the machine measurements value consistent with the stan da...

Page 15: ...ire Various connecting wire must be well connected with the terminal otherwise it would result in reducing the reliability of machine When connecting the wire please separate power supply relays senso...

Page 16: ...Humidores Wacota 2016 Humidores Wacota Oficina Benet ser 25 28049 Madrid Espa a F brica C Enebro 8 10 12 28100 Arganda del Rey Madrid Tel 34 911 728 634 34 609 464 567 info wacota com www wacota com...

Reviews: