Specifications
17
Dual-LIte
®
TRX
™
MBC
™
3.1
Electrical Characteristics
Table 8
Weights—Dual-Lite TRX UPS, 10-30kVA, and 200mm Dual-Lite TRX MBC
UPS Rating, kVA
UPS Weight
lb (kg)
Dual-Lite TRX
MBC 200mm
Weight, lb (kg)
Combined Weight
UPS and Dual-Lite
TRX MBC, lb (kg)
10
684 (310)
198 (90)
882 (400)
15
684 (310)
198 (90)
882 (400)
20
684 (310)
198 (90)
882 (400)
30
758 (344)
198 (90)
956 (434)
Table 9
Additional weight for Dual-Lite TRX 10-30kVA UPS with internal batteries *
Battery Model
Battery
Code
Added Battery
Weight, lb (kg)
12HX150-FR
H
624 (283)
12HX205-FR
M
1032 (468)
* For total system weight, add the weight for the UPS and Dual-Lite TRX MBC
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect
breaker must be provided for AC input, Bypass and AC output. Recommended cable sizes are
suitable for operation at a maximum temperature of 104°F (40°C).
Table 10
Dual-Lite TRX MBC input currents, single input, main
Voltage
3-Ph, 60 Hz
MBC
Rating
kVA
System
Input
Current
A, Max
Phase
Recommended
Upstream
Protection, A
75°C
Wire
Current
A, Total
Copper
Wire
Aluminum
Wire
Bolt
Size
208/120
220/127
10
34
3W + N + G
45
65
(1) #6
(1) #4
M10
208/120
220/127
15
51
3W + N + G
70
85
(1) #4
(1) #2
M10
208/120
220/127
20
68
3W + N + G
90
115
(1) #2
(1) 1/0
M10
208/120
220/127
30
102
3W + N + G
150
175
(1) 2/0
(1) 4/0
M10
Table 11
Dual-Lite TRX MBC output currents
Voltage
3-Ph, 60Hz)
MBC
Rating, kVA
System
Output
Current
A, Max
Phase
Recommended
Upstream
Protection, A)
75°C
Wire
Current
A, Total
Copper
Wire
Aluminum
Wire
Bolt
Size
208/120
220/127
10
28
3W + N + G
40
50
(1) #6
(1) #4
M10
208/120
220/127
15
42
3W + N + G
60
85
(1) #4
(1) #2
M10
208/120
220/127
20
56
3W + N + G
70
115
(1) #2
(1) #2
M10
208/120
220/127
30
83
3W + N + G
110
130
(1) 1/0
(1) 2/0
M10