12
(4)Test generator
VI.The use of discharge rod
1. The special discharge rod should not be in direct contact with high-voltage DC
discharge, and should be kept at a distance. When the tip of the discharge rod initially
produces corona discharge, and the voltage on the test object gradually drops by 20% of
the test voltage, then touch the discharge rod to the shell of the microammeter. discharge.
Finally, hang the ground wire of the grounding end of the discharge rod directly on the test
object.
2. Special attention is not allowed to directly discharge the ground wire on the shell of the
high-voltage microammeter, so as to avoid the damage of the high-voltage microammeter
caused by the strong impulse discharge current.