8
current.
2. Boosting voltage parameter Settings
Voltage booster section number setting: set according to the actual use of voltage
booster section.It is used to adjust the voltage ratio of the inner part.
Test voltage setting: refer to the P 4-4.3 and P 4-4.4,this parameter is used for setting
manual and automatic voltage boost and timing trigger.
Over-voltage setting: it is used to protect the sample from being broken down when
testing sample votlage exceeds the normal allowable voltage value due to the wrong
operation.
Current limiting setting: refer to P 4-4.4,when the current exceeds this setting value, the
system will cut off the high voltage.
Setting of voltage boosting time:refer to P 4-4.4, when the voltage rises to the test
voltage, the initial value of pressurizing time is used to start the countdown.
Test current setting: refer to P 4-4.5,in the MOA booster test mode, this value is
generally set to 1000uA, and the system is shielded from other Settings. (when displaying the
sample current, take it as the reference value).
Test time setting: refer to P 4-4.5,in the MOA booster test mode, the test current holding time
will automatically drop to 0.75 times of the current voltage after the timing.
0.75 time setting: refer to P 4-4.5, in the MOA booster test mode, the time should be
maintained after the voltage drops to 0.75 udc-1ma, and the system will automatically reduce
the voltage to zero after the 0.75 time is timed.
3. Boost interface (refer to P 4-4.6)
It mainly display voltage and current, the system is also through the dialog box to display the
test process information. These include voltage holding time and all kinds of protection
information tips.
A) Save test results(refer to P 4-4.7)
When the pressurization test is completed, the system will display the parameters captured
during the pressurization and prompt to save the record.
B) Record query( refer to P 4-4.8)
This function is used to browse the previously saved test records.