When the test time or manual stopped, display shows as shown in the table of the soft

keys.

Soft key

Description

OFF

Power Off (No operation, 3 minutes automatic shutdown)

Back

Return to the main menu

H.V

Set test voltage:

Manual

500V

1000V

2500V

5000V

10000V

15000V

Rt

Veiw 15S

30S

60S

600S Insulation value

Manual voltage regulation function

Digital

Insulation value

( >

greater than

; <

less than

)

Measured time

actual voltage

Battery Indicator

H.V

warning

Leakage current

1mA=1000uA
1uA =1000nA

Set Voltage

Regulating key

Soft key

Description

Regulating key +

By a voltage rise of 10V, long time boost up,

the fastest up to 600V per second.

Regulating key -

According to a voltage drop 10V, long time

step-down speed up, the fastest u

Stop

measuring

In manual voltage regulation, due to the use of 3 and 4 keys,
only 1, 2 keys and start stop keys can be used to stop the
measurement operation.

When the test time or manual stopped, display shows as shown in the table of the

soft keys.

Soft key

Description

OFF

Power Off (No operation, 3 minutes automatic shutdown)

Back

Return to the main menu

H.V

Set test voltage:

Manual、

500V

1000V

2500V

5000V

10000V

15000V

20000V

Rt

Veiw 15S

30S

60S

600S Insulation value

Set Voltage:

Summary of Contents for HZJY-15K

Page 1: ...HZJY 15K Insulation Resistance Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...Contents I Warning 1 II Feature 2 III Specification Parameter 2 IV Introduction of Instrument 3 V Instrument Using 7 VI Packing List 8...

Page 3: ...erators in instrument surface operation Please don t charged the connection test line low Low in the measurement or do not touch the circuit being measured immediately after the test may result in ele...

Page 4: ...eaches 2 mA still ensure accuracy of test instruments 2 methods for power use of lithium ion batteries battery life can be up to 4 hours 10000V 100M Insulation resistance simulation column Digital fil...

Page 5: ...tance testing range and accuracy T 23 5 C RH 45 75 range accuracy 500V 1000V 2500V 5000V 10000V Unspecified 1M 1M 1M 1M 1M 5 1M 10G 1M 20G 1M 100G 1M 100G 1M 200G 20 10G 100G 20G 200G 100G 1T 100G 1T...

Page 6: ...iption OFF Power Off No operation 3 minutes automatic shutdown H V Set test voltage Manual 500V 1000V 2500V 5000V 10000V 15000V TIME SetThe test time 01 00 10 00 30 00 Switching software keys to a new...

Page 7: ...p 1 In shutdown state hold key 2 the 2 key 2 Press the 1 key the power button until into the contrast adjustment menu 3 Press 1 or 2 keys to adjust contrast until the right 4 Press the 4 key save and...

Page 8: ...Regulating key Soft key Description Regulating key By a voltage rise of 10V long time boost up the fastest up to 600V per second Regulating key According to a voltage drop 10V long time step down spe...

Page 9: ...e polarization index after 600 seconds Polarization index calculation method PI R600 R60 test connection points for attention 1 Tested to confirm product safety grounding try not charged 2 Confirm the...

Page 10: ...8 VI Packing List No Item Qty 1 Main engine 1 2 Power line 1 3 Red test line 1 4 Black test line 1 5 Green test line 1...