6

Button

Operate instruments. “↑↓” is the "up and down" key, select to move or modify
data; “←→” is the "left and right" key, select to move or modify data; "Enter"
key, confirm the current operation; "Cancel" key, abandon the current
operation.

Function

module

Instructions

Power
switch

The power switch of the whole machine is switched to the open position
when it is switched on. Switch to the close position when it is switched off.

RS 232

interface

Connect external printer.

Charging

interface

Use instrument charger to recharge.

USB

interface

External USB disk is used to store test data, please use FAT or FAT32
format U disk; in the storage process, it is strictly prohibited to dial out the
USB disk.

X.Operation Instructions

Single phase transformer or single phase PT test wiring

The yellow and green test clamps of the red test line at the high-voltage test end

are connected to the high-voltage end of the tested product, and the yellow and

green test clamps of the black test line at the low-voltage test end are connected to

the low-voltage end of the tested product.

Single phase CT test wiring

The yellow and green test clamps of the red test line at the high voltage test end

are connected to the second side of the tested product, and the yellow and

green test clamps of the black test line at the low voltage test end are connected to

the first side of the tested product.

Test wiring for three phase transformer

The yellow, green and red test clamps of the red test line at the high-voltage test

end connect the A, B and C phases at the high-voltage end of the tested product;

the yellow, green and red test clamps of the black test line at the low-voltage test end

connect the a, B and C phases at the low-voltage end of the tested product.

Intelligent power management

When the instrument is not operated for a long time, the LCD backlight is

automatically dimmed to save power; the instrument has the function of charging

Summary of Contents for HZBB-10S

Page 1: ...HZBB 10S Portable Transformer Turns Ratio Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...manual and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this...

Page 3: ...aging Content 1 IV Functional Characteristics 2 V Technical Indicators 2 VI Adjust The Wristband 3 VII Battery Charging 3 VIII Tilt Hand held Tester 4 IX Product Appearance 4 X Operation Instructions...

Page 4: ...e battery without authorization When the instrument or battery fails please return to the factory II Introduction Hand held transformer turn ratio tester is an innovative product with compact size han...

Page 5: ...e polarity test function of CT variable ratio is added and the application field is wider Wide range and high accuracy the variable ratio measurement range can reach 10 000 and the test accuracy can b...

Page 6: ...ure 10 50 Relative humidity 90 No dew VI Adjust The Wristband For better grip strip the belt and adjust the adhesive tape as shown in the following figure VII Battery Charging When the battery is low...

Page 7: ...ld Tester In order to take the instrument or expose the side interface during operation the hand held tester can be tilted as shown in the figure below Lift the tilt seat and pull outward IX Product A...

Page 8: ...yellow and green test lines are connected to single phase test Low voltage test terminal The yellow green and red three color junction bases correspond to the three phase of a B and C respectively an...

Page 9: ...ted to the high voltage end of the tested product and the yellow and green test clamps of the black test line at the low voltage test end are connected to the low voltage end of the tested product Sin...

Page 10: ...of printer paper tear the teeth out a little bit Close the cover and press the print head to the print head Press the print head back to the print head with a bit of force Operation instruction After...

Page 11: ...e of the instrument Need a password operation it is not open to the user 5 SV Display software current version number HV Display hardware current version number The function and operation of are descr...

Page 12: ...e connection mode and connection group of the tested products Group When the user chooses the known connection mode the measurement and display of the instrument are based on the user s input When the...

Page 13: ...strument detects short circuit high and low voltage reverse connection fault the display screen will pop up the fault alarm box and stop measuring The three phase ratio test results screen is shown be...

Page 14: ...ing according to the high side pressure regulating design is to assume that one point as the highest voltage range if the voltage reverse design or tap changer in low voltage side of transformer displ...

Page 15: ...12 XII Packing List No Item Qty 1 Main engine 1 2 Red test line 1 3 Black test line 1 4 Print paper 2 5 Power line 1...

Reviews: