(3) During actual wiring, the current output terminal should form a loop, otherwise the

instrument will not output current.

(4) The current booster comes with random output wires; the output external copper wire

is selected according to 10A/mm2. (The standard configuration is two 3m test leads)

(5) The capacity of the equipment is designed for short-time work of 5 minutes. If used for

batch test, the working time should be less than 2.5 minutes, wait for 10 minutes before

proceeding to the next work. Such as temperature rise (30 minutes-24 hours) should be

prepared according to long-term working temperature rise.

II.Technical Features

1. Name and Classification

(1) Name: HZ5372 high current generator.

(2) Environmental group: it belongs to the

group of instruments (that can be used in

outdoor environment) in GB6587.1-86 "General Outline of Environmental Test of

Electronic Measuring Instruments".

2.1 Input voltage: AC220V ±10%

2.2 Power: 5KVA

2.3 Output current: Series: AC0

1000A Parallel: AC00

2000A stepless adjustable,

panel with digital display ammeter

2.4 Output voltage: (>10V)

2.5 Output Waveform: The output current is a standard sine wave with tiny burrs, which is

better than the power system requirements and standards, and the ripple coefficient is

less than 0.3%. Standard sine wave.

2.6 Measurement accuracy: (using 0.2S grade material) is actually around 0.3; each

current can be smoothly and continuously adjustable, and the accuracy is higher than 0.5.

The current and voltmeter display is a true effective value, with high accuracy and high

stability.

2.7 Output current mode: the true effective value is continuously adjustable;

2.8 Current stability: 0.2%

2.9 Structure: One

Reviews: