background image

6

menu. The cursor is in current selection. Item Press the select key to select the

measurement current. When the current is 100A or 200A, the cursor is in the time

selection item. Press the select key to cycle selection between 10 seconds, 30 seconds,

1 minute, 5 minutes, 10 minutes, and continuous , When the current is selected as 300A,

the cursor can be cycled between 10 seconds, 30 seconds, 1 minute, and press the

selection key in the time selection item. Press the start key at any time to enter the

measurement state.

2. Operation steps:

1) Complete the wiring of the instrument end and the end of the tested product as

required

2) After powering on, press the select button to select the appropriate measurement time

and measurement current, press the start button to start the current, the screen displays

"charging", a few seconds later it displays "testing", and a few seconds later it displays

the measured resistance Value and current value, after the measurement is completed,

the display is shown in Figure 2

Figure 2

According to the interface prompts, press the select key to print the measurement results,

and press the cycle key to store the measurement results in the U disk. When the reset

button is pressed during the test or the test is over, the output current of the instrument

becomes zero. After the measurement is over, the power should be turned off first, and

then the lead wire should be removed to prepare for the next test

3) In Figure 1, press the cycle key to move the cursor to the host parameter, press the

select key to enter the interface as shown in Figure 3.

Summary of Contents for HZ-5300

Page 1: ...HZ 5300 Contact Resistance Tester User Manual Huazheng Electric Manufacturing Baoding Co Ltd...

Page 2: ...and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this instrum...

Page 3: ...what will you notice before testing III Brief Introduction Working theory V Technical parameter VI PLC interface VII Operation Instructions and Procedures VIII Applying Illustration IX Calibration X...

Page 4: ...artments Claim The output current and measuring resistance are simultaneously output on the 65K true color LCD and the measurement results can be voltage output or stored in a USB flash drive The powe...

Page 5: ...lution min 0 1 Accuracy 0 5 2 words Power 1000W Working mode continuous measurement Power supply AC220V 10 50HZ Operating temperature 0 40 Relative humidity less than or equal to 90 without condensati...

Page 6: ...Press this key to select various settings of the instrument and the data can be printed after measurement 9 Circulation key main menu cycle selection key or U disk storage 10 Confirm key Press the con...

Page 7: ...ropriate measurement time and measurement current press the start button to start the current the screen displays charging a few seconds later it displays testing and a few seconds later it displays t...

Page 8: ...to move the cursor to the clock to modify press the select key to enter the interface as shown in Figure 4 Figure 4 Press the cycle key to move the cursor between each date data press the select key...

Page 9: ...uld be removed first 1 Wiring method As shown in Figure 6 connect the dedicated test wire to the corresponding I and I terminals according to the color red to red black to black and tighten the thin p...

Page 10: ...sed to measure loop resistance and it is not allowed to measure inductive loops After sales service The instrument will be repaired and replaced free of charge for product quality problems within one...

Reviews: