Fig.8 Test parameter setting
●
Test ID :
Set the current test number.
●
Device ID:
The number of the device being tested, which cannot be set.
●
Test Mode:
The test mode can be wired, wireless and induction. When choosing wireless test mode,
the number at the right of the word "wireless" indicates the channel value used by the
current wireless module.
●
Reference:
Reference phase.It can be set as ABC, A, B, C, A-B and C-B;
when selecting the
induction test mode, it is fixed to phase B.
The ABC represents the simultaneous use of the three-phase voltage as the
reference voltage.
The A, B, and C indicate the use of the single-phase voltage as the reference
voltage.
A-B and C-B indicate the case where the phase B of PT is grounded,using A-B
or C-B as the reference voltage.
When the single-phase voltage is used as the reference voltage, the reference
voltage is input by phase A of the voltage collector(yellow wire) channel.
●
Tested
:
Tested phase.It can be set as ABC, A, B and C.
ABC represents three-phase simultaneous measurement, namely three phase
currents is entered simultaneously in the three phase current channels of A,B and
C .
A, B, and C represent single phase measurement, and phase A current
channel is used to input current.
●
COMP Mode:
Compensation mode.It can be set as"No COMP", "Manual COMP"and "Auto COMP".
"No COMP": disable compensation.Namely the compensation angle is 0°. When the