Huayu(Ningbo)New Energy Technologies Co.,Ltd. All rights reserved.
c
4.5 Backup/Clear Data
4.6 Status Bar
Figure 12 Communication Address Setting
Figure 13 Backup/Clear Data
When a USB flash disk is inserted, press the Save/Clear button to call up the following dialog box (see Figure 13).
Press the Save button, and press “Yes” on the confirmation window that appears to compress and backup all
collected data to the USB flash disk. The document will automatically use the backup date for its name.
Press the Reset button, and press “Yes” on the confirmation window that appears to clear all collected data.
The device settings will not be changed.
The bottom field on all display pages consists of the status bar, which displays the device's operating status,
the current IP address, and the current date and time. “OK” means that the device is operating normally.
A 16-bit error code will be displayed in the form of a hex number if there happens to be a malfunction. The
meaning of the error code is listed as the following table.
07
Error code
Bit-0
Bit-1
Bit-2
Bit-3
Bit-4
Bit-5
Bit-6
Bit-7
Error
DC over voltage
DC under voltage
hardware error
Inverter over voltage
Frequency over
Frequency under
AC voltage RMS over
AC voltage RMS under