5
8. Cut off the cable ties binding holes of copper bars
numbered 23, 24, 25, 26, and 30. Install the soft
copper bars in the bypass cabinet and its adjacent
power cabinet from inside out.
9. Remove the filler panel from the
power cabinet, and install the soft
copper bar numbered 52.
10. Reinstall No. 10 protective plate removed in Step 6.
11. Insert the cable terminals of the bypass cabinet into the corresponding ports on the parallel
board of the power cabinet. The parallel board is located at the rear of the power cabinet
adjacent to the bypass cabinet and it can be seen after the rear cover is removed.
Bypass Cabinet
Cable Name
Bypass Cabinet Cable Label or Number
Port Silk Screen on the
Power Cabinet Parallel
Board or Cable Number
Quantity
Bypass module
DL37 cable
W301_J21
J21
1
W303_J24
J24
1
ECM 8-pin cable
W305_J22
J22
1
ECM system
monitoring bus
W307_J25
J25
1
CT cable
W309_J26
J26
1
Switch cable
Full configuration: 04091625-06
Standard configuration: SW1310
04091626-23
1