Step 10
Route signal cables. Bind cables to the cabinet.
shows the signal cables routed
from the top of the cabinet.
Do not bind signal cables and power cables together.
Figure 3-86
Routing signal cables from the top of the cabinet
The number and colors of signal cables in
----End
Follow-up Procedure
After connecting cables, reinstall the covers of the power distribution subrack, rear panel,
and side panel of the bypass cabinet.
After connecting cables, check that a certain clearance is reserved between the internal
switch (if any) extension pole and power cables to avoid friction.
3.2.7.2 Bottom Cable Routing
Context