4. Connect battery cables, AC output power cables, fire protection cables and generator Start/Stop
cables.
Neutral cables
Battery cables
PE cables
IT and smart cooling product output power
cables
Lighting cables
Fire Protection and Generator
Start/Stop Cables (ATS input cabinet)
Port Description
Bolt Specifications
Bolt Length
Torque
AC input
M12
45 mm
46 N·m
Battery input
M10
30 mm
26 N·m
PE
M12
45 mm
46 N·m
Safe grounding
M6
16 mm
4.5 N·m
Route a neutral wire from the middle of the
positive and negative battery strings.
Take a battery string consisting of 40 batteries
as an example. A neutral wire is routed from the
middle of positive and negative battery strings,