1.3.5 Connecting a Remote EPO Switch
NO TICE
● The product is not provided with an EPO switch or cable. Prepare them by
yourself before installation. The recommended cable is 22 AWG.
● Equip the EPO switch with a protective cover to prevent misoperations, and
cover the cable with protective tubing.
● Triggering EPO will shut down the rectifier, inverter, charger, and static bypass,
but does not disconnect the UPS mains input. To power off the UPS completely,
you can turn off the upstream input switch when you trigger EPO.
Connect the EPO switch to the specified dry contact on the UPS using a cable.
NO TE
By default, the EPO switch is off. When it is turned on, EPO is triggered.
Figure 1-66 Cable connection for an NO EPO switch
1.4 Installing a Parallel System
Procedure
Step 1 Ground each UPS in a parallel system separately, and connect power cables and
battery cables.
Step 2 Select a parallel mode and connect cables to the parallel system based on site
requirements.