Step 4 Switch off the external battery circuit breaker for each UPS or the general battery
circuit breaker (when all UPSs in the parallel system share a battery string). If no
external battery circuit breaker is configured, disconnect battery power cables
from each UPS.
----End
5.3.3 Performing EPO
Turn on the EPO switches (provided by the customer). The UPSs enter the EPO
state. That is, the UPSs shut down the inverters, and do not transfer to the bypass
mode.
Figure 5-10 EPO cable connection in a parallel system
UPS2000-G-3KRTLL
User Manual
5 Operations
Issue 01 (2020-10-26)
Copyright © Huawei Technologies Co., Ltd.
101