UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
64
Figure 5-11
Setting the voltage and frequency
Step 6
Set the number of batteries based on the actual battery capacity. The default value is 16 for
the UPS with long backup time, and the value can range from 16 to 20.
Figure 5-12
Setting the number of batteries
Step 7
Set the battery capacity to the total capacity of all batteries actually connected. The default
value is 40 Ah for the 6 kVA UPS with long backup time. The default value is 65 Ah for the
10 kVA UPS with long backup time, and the value can range from 7 Ah to 999 Ah.
Figure 5-13
Setting the battery capacity
Step 8
Set the charge current limit based on actual conditions. The default value is 2.0 A for the UPS
with long backup time, and the value can range from 1.0 A to 12.0 A, the interval is 0.5 A.
Figure 5-14
Setting the charge current limit
Step 9
Start the UPS in normal mode by using one of the following methods: