UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
4 Control Panel
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
52
Name
Screen
Function
Value
Range
Preset
Value
Remarks
Total
battery
capacity
Set the battery
capacity. (The
battery capacity is
the total capacity
of battery strings
and is set based on
the actual
capacity.)
7–999 Ah
6 kVA
with
long
backup
time:
40 Ah
10
kVA
with
long
backup
time:
65 Ah
The value is
configurable
in non-battery
mode or non-
battery ECO
mode.
Charge
current
limit
Maximum charge
current in
equalized charge
mode. The interval
is 0.5 A.
1.0–12.0 A
2.0 A
The
parameter is
configurable
in any mode.