UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
4 Control Panel
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
54
Name
Screen
Function
Value
Range
Preset
Value
Remarks
Discharge
time
protection
setting
Set the maximum
discharge time.
When the
discharge time
reaches the value,
the system powers
off. If you set the
value to 0, the
discharge time is
not limited.
0–24 hours
16 hours
The value is
configurable
in non-battery
mode or non-
battery ECO
mode.
ECO
mode
enabling
Indicates whether
to allow a single
UPS to work in
ECO mode.
DIS
(disabled)
and ENA
(enabled)
DIS
The value is
configurable
only after the
inverter shuts
down.