Alarm ID Alarm
Name
Alarm
Severity
Possible Cause
Troubleshooting Suggestion
2036
Grid
Overfreq
uency
Major
Cause ID = 1
Power grid exception: The
actual grid frequency is
higher than the
requirement of the local
power grid standard.
1. If the alarm occurs
accidentally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs
frequently, check whether the
grid frequency is within the
acceptable range. If no,
contact the local power
operator. If yes, log in to the
mobile phone app,
SmartLogger, or NMS to
modify the grid
underfrequency protection
threshold with the consent of
the local power operator.
2037
Grid
Underfre
quency
Major
Cause ID = 1
Power grid exception: The
actual grid frequency is
lower than the requirement
of the local power grid
standard.
1. If the alarm occurs
accidentally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs
frequently, check whether the
grid frequency is within the
acceptable range. If no,
contact the local power
operator. If yes, log in to the
mobile phone app,
SmartLogger, or NMS to
modify the grid
underfrequency protection
threshold with the consent of
the local power operator.
SUN2000-(3KTL-10KTL)-M0
User Manual
7 Maintenance
Issue 06 (2020-10-23)
Copyright © Huawei Technologies Co., Ltd.
73