5. After the green indicator of the BCU blinks at super short intervals and the red indicator is 

steady on, switch on the battery circuit breaker on the battery cabinet.

SmartLi 3.0 Quick Guide (Short-Term Backup Power)

Not Communicating with the UPS

1. On the UPS LCD, choose System Info. Settings Battery Settings and set the parameters 

as follows (the batteries are managed as lead-acid batteries by default. The battery type 
displayed on the NMS is VRLA batt, but actually lithium batteries are connected to the UPS).

Set the preceding parameters and retain the default values for other parameters.

The preceding parameters are described for Huawei UPS5000 series. For third-party UPSs, 
set the parameters by referring to the preceding description. If parameters are different, 
contact technical support.

If the preceding parameters are incorrectly set, the SmartLi cannot be charged or 
discharged properly. In this case, contact technical support.

Item

Description

Setting

Battery type

Specifies the type of batteries 
connected to the UPS.

VRLA batt.

Single battery 
voltage (V)

Specifies the voltage of each 
battery that is connected in 
series in a battery string.

2

12

Single battery 
capacity (Ah)

Specifies the capacity of each 
battery that is connected in 
series in a battery string.

9999 (maximum value)

Batteries in a 
battery string

Specifies the number of 
batteries in a battery string.

8+8/8+0 scenario:
Recommended value: 
276
Value range: 276–300

8+8/8+0 scenario:
Recommended 
value: 46
Value range: 46–50

7+7/7+0 scenario:
Recommended value: 
252
Value range: 240–270

7+7/7+0 scenario:
Recommended 
value: 42
Value range: 40–45

6+6/6+0 scenario
Recommended value: 
204
Value range: 192–234

6+6/6+0 scenario
Recommended 
value: 34
Value range: 32–39

Number of 
battery strings

Specifies the number of 
battery strings connected in 
parallel.

1

Cell float 
voltage (V/cell)

Specifies the battery float 
charging voltage.

2.3

Cell equalized 
volt. (V/cell)

Specifies the battery equalized 
charging voltage.

2.3

Dis. cur. 0.1C 
EOD (V/cell)

Specifies the EOD threshold 
when the discharge current is 
0.1C, 0.3C, 0.5C, or 1.0C 
respectively.

1.8

Dis. cur. 0.3C 
EOD (V/cell)

1.8

Dis. cur. 0.5C 
EOD (V/cell)

1.75

Dis. cur. 1.0C 
EOD (V/cell)

1.75

If a third-party UPS is 
connected and the EOD is 
not distinguished by rate, set 
this parameter to 1.8 V/cell.

If a third-party UPS is connected, set 
this parameter to the maximum value.

If the UPS from the Company is 
connected, set Batt. charging capacity 
mismatch 
to Disable on the WebUI.

The following operations apply to the scenario where SmartLi 3.0 does not communicate 
with the UPS (no communications cable is connected between the SmartLi and the UPS).

The preceding procedure applies to the single-cabinet scenario. For the multi-cabinet 
scenario, see 

SmartLi 3.0 User Manual (Short-Term Backup Power)

.

The BCB off alarm (the red indicator is steady on) is displayed on the SmartLi LCD. No action is 
required. After the battery circuit breaker is switched on, the alarm will be automatically cleared.

The green indicator blinks intermittently.  After 1 minute, the BCU starts. The green indicator blinks 
at super short intervals and the red indicator is steady on.

If multiple SmartLi cabinets are connected in parallel, press and hold the POWER ON/OFF button 
on the BCU of the master cabinet for more than 2s to power on the master cabinet. Then, power 
on slave cabinets one by one in the same way.

2. Press and hold the POWER ON/OFF button on the BCU of the SmartLi cabinet for more than 2s. 

The green indicator of the BCU blinks at short intervals.

4. Set the language, time, date, cloud service, network parameters, system 

parameters, and alarm parameters on the Settings Wizard screen of the SmartLi.

5

3. Obtain authorization on the battery cabinet.

System User

LCD Preset 
Password

WebUI Preset 
Password

admin 
(administrator)

000001

Changeme

operator 
(common user)

000001

Changeme

To ensure system 
security, change the 
preset password 
after login.

4. On the UPS LCD, choose System Info. Settings Battery Settings and set 

Battery Type to Lithium battery.

The UPS from the Company requires that 
the equalized  charging voltage be higher 
than the float charging voltage, so the 
equalized charging voltage should be 0.01 
V higher. For third-party UPSs, comply with 
similar requirements  if applicable.

Summary of Contents for SmartLi-512V-162Ah-F

Page 1: ...ncluding the Insulation Layer Unit mm Recommended Cable Size Unit mm2 M40 10 32 Innermost layer white 10 16 Innermost layer white second to last layer red 16 22 70 95 120 The single core 90 C resistant flexible copper cable is used as an example in the table to illustrate which sealing plugs need to be removed The sealing plugs to be removed depend on the actual cable diameter including the insula...

Page 2: ...nd crimp the DT terminal Marked DT terminal direction Marked cable cutting position 1 Set the switch based on the actual load Installing Output Power Cables 250 kW Load of a single battery cabinet 300 kW 200 kW Load of a single battery cabinet 250 kW Load of a single battery cabinet 200 kW 2 Install power cables UPS Without a Neutral Wire UPS With a Neutral Wire Connect cables correctly to avoid b...

Page 3: ...battery strings and the cabinet It is recommended that you use the DC voltage mode of a multimeter to measure the voltage between the battery tray and the positive and negative terminals of each battery string respectively If the readings are less than 6 V DC the insulation is good Otherwise contact technical support engineers 8 Attach PP sheets to the notches of the battery modules on the top lay...

Page 4: ...easures for example using a dust cover plastic film or fabric cloth to prevent battery condensation or dust corrosion Remove the protective material when batteries need to be used The BCB off alarm the red indicator is steady on is displayed on the SmartLi LCD No action is required After the battery circuit breaker is switched on the alarm will be automatically cleared The green indicator blinks i...

Page 5: ...when the discharge current is 0 1C 0 3C 0 5C or 1 0C respectively 1 8 Dis cur 0 3C EOD V cell 1 8 Dis cur 0 5C EOD V cell 1 75 Dis cur 1 0C EOD V cell 1 75 If a third party UPS is connected and the EOD is not distinguished by rate set this parameter to 1 8 V cell If a third party UPS is connected set this parameter to the maximum value If the UPS from the Company is connected set Batt charging cap...

Page 6: ... Number of lead acid batteries supported is 252 42 x 12 2 252 in the 7 7 7 0 scenario 8 8 8 0 scenario 276 8 8 8 0 scenario 276 300 7 7 7 0 scenario 252 7 7 7 0 scenario 240 270 6 6 6 0 scenario 204 6 6 6 0 scenario 192 234 Battery cabinet quantity Specifies the number of battery cabinets connected in parallel Currently a maximum of 10 lithium battery cabinets can be connected in parallel 1 1 10 A...