R4815N1 Rectifier User Manual V1.2 

Indicator 

Color 

Status 

Description 

 Measures 

Power 
indicator 

Green 
 

Steady on  The rectifier is supplied with alternating current 

(AC) input power. 

The rectifier runs properly, and no 
measure is required. 

Off 

The rectifier is not supplied with AC input power. 

Replace the rectifier if the AC input is 
normal. 

The rectifier is faulty. 

Replace the rectifier. 

Blinking at 
0.5 Hz 

The rectifier is being queried. 

No measure is required. 

Blinking at 
4 Hz 

The rectifier is loading an application program. 

The rectifier automatically recovers after 
loading, and no measure is required. 

Alarm 
indicator 
 

Yellow  Off 

No alarm is generated. 

The rectifier runs properly, and no 
measure is required. 

Steady on  The rectifier generates a prewarning for power 

limiting due to overtemperature. 

The rectifier generates an alarm for shutdown due 
to ambient overtemperature protection. 

Check that the air vent is not blocked 
and the ambient temperature is within a 
normal range. 

The rectifier generates an alarm due to AC input 
overvoltage or undervoltage protection. 

Check that the electrical grid voltage is 
within a normal range. 

The rectifier is hibernated. 

No measure is required. 

Blinking at 
0.5 Hz 

The rectifier communication is interrupted. 

Replace the rectifier or monitoring 
module. 

Fault 
indicator 

Red 
 

Off 

The rectifier is not faulty. 

No measure is required. 

Steady on  The rectifier is locked due to output overvoltage. 

Pull out the rectifier and reinsert it after  
1 minute. 

There is no output because the rectifier is faulty. 

Replace the rectifier. 

The high -voltage power supply energize equipment. Contacting the high-voltage power supply directly or through a 
dampened object may cause you to death. 

Improper operations on the high-voltage power supply may cause accidents such as fire or electric shock. 

Maintenance 

Suggestions 

1. Rectify the faults by referring to Table 2. 

2. If you cannot rectify the fault according to Table 2, replace the rectifier. 

3. Return the faulty rectifier to Huawei for repairing. 

 

Huawei technical support website: 

 

http://support.huawei.com 

Base on following suggestion, Simple fault can be dealt with. 
Table 2 Describes the states of LEDs and the causes for abnormal. 

DANGER

Huawei Technologies Co., Ltd. 

Huawei Industrial Base 

Bantian, Longgang, Shenzhen

   

 

518129 

www.huawei.com 

Summary of Contents for R4815N1

Page 1: ... V AC 30 100 load Height x Width x Depth 40 8 mm x 95 5 mm x 208 mm 1 61 in x 3 76 in x 8 19 in Weight About 1 1 kg Cooling Built in fan The rotation of fan depends on the internal temperature Description The R4815N1 is a digital rectifier with high efficiency and power density It converts 85 300 V AC input voltage to 53 5 V DC output voltage The output voltage can be adjusted by the host It perfo...

Page 2: ...ong term short circuit is allowed After the fault is rectified the rectifier is restored to a healthy state automatically Over temperature protection The module protects against overtemperature Safety EMC Lightening protection Safety certification Passes TUV CE UL certifications Catch the CB certificate Complies with UL60950 1 IEC60950 1 EN60950 1 CAN CSA C22 2 No 60950 1 EMC EN55022 Class B EN550...

Page 3: ... the guide rail and push the locking latch right to fix the handle as shown in Figure 6 Transport The product must be packed with firmly packing box when transport Out of the box the mark prevent moisture lay down carefully and other required mark must have Any transport tools are permitted if the product in the packing box When transport must avoid rain and snow attack directly and mechanical sho...

Page 4: ...voltage protection Check that the electrical grid voltage is within a normal range The rectifier is hibernated No measure is required Blinking at 0 5 Hz The rectifier communication is interrupted Replace the rectifier or monitoring module Fault indicator Red Off The rectifier is not faulty No measure is required Steady on The rectifier is locked due to output overvoltage Pull out the rectifier and...

Reviews: